2014-05-01 18:09:40PLUMBING PLAN REVIEW
 LOFTIN PLACE -FOUNDATION PERMIT
 PERMIT: 14020547
 ADD: 705 N OLIVE AVE
 CONT: KAST CONSTRUCTION
 TEL: (561)689-2910
 CONTACT: NEYITA (561)856-6655
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: THURSDAY MAY 01/2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS:
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.3 PLUMBING
 SANITARY DRAINAGE
 VENTS
 ROOF DRAINAGE
 SAND INTERCEPTOR OR TRAPS
 ENVIRONMENTAL REQUIREMENTS
 PLUMBING RISER
  
 2A) 2ND REQUEST, SHEET P-2.1.1.A INDICATES A 8 INCH
 PIPE FOR GARAGE DRAINAGE TO SAND FILTER SEE CIVIL DWGS,
 IF THE PLANS SHOW A SAND FILTER TO GET RID OF OILY
 WATER PLEASE PROVIDE DETAILS FOR SUCH FILTER. AS IN
 YOUR RESPONCE PARKING GARGES DO NOT REQUIRE THE SAND
 FILTER BUT YOU AS THE DESIGNER REQUIRE IT, SHOWN ON
 TTHE PLANS THEN WE WILL NEED THE BACK UP LITERATURE FOR
 THE SIZING OF THE SAND FILTER.
  
 PLEASE COMPLY WITH 2010 FBC-P 1003.1 WHERE REQUIRED.
 INTERCEPTORS AND SEPARATORS SHALL BE PROVIDED TO
 PREVENT THE DISCHARGE OF OIL, GREASE, SAND AND OTHER
 SUBSTANCES HARMFUL OR HAZARDOUS TO THE BUILDING
 DRAINAGE SYSTEM, THE PUBLIC SEWER, THE PRIVATE SEWAGE
 DISPOSAL SYSTEM OR THE SEWAGE TREATMENT PLANT OR
 PROCESSES.
  
 2B) 2ND REQUEST. 1003.11 (IPC 1003.5) SAND INTERCEPTORS
 IN COMMERCIAL ESTABLISHMENTS. SAND AND SIMILAR
 INTERCEPTORS FOR HEAVY SOLIDS SHALL BE DESIGNED AND
 LOCATED SO AS TO BE PROVIDED WITH READY ACCESS FOR
 CLEANING,AND SHALL HAVE A WATER SEAL OF NOT LESS THAN 6
 INCHES (152 MM).
  
 2C) COMPLIED.
  
 2D) 2ND REQUEST, THIS MAY BE A FOUNDATION PERMIT BUT
 THE ROOF DRAINAGE IS SIZED FROM THE ROOF AREA AND 1/2
 OF THE HEIGHT OF THE PARAET WALLS, THE PLANS ALSO FAIL
 TO PROVIDE THE CRITERIA FOR SIZING OF THE ROOF
 DRAINAGE, 2010 FBC-P 1106.1 WITH OUT THIS INFORMATION
 WE CAN NOT BE SURE THE CONDUCTORS ARE SIZED PROPERLY.
 100 YEAR 1 HOUR RAIN FALL 4,5 INCHES.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.5.1.3
 PLUMBING ROOF DRAINAGE ISOMETRIC FOR THE BUILDING.
 PLEASE NOTE THE SHEET INDICATED IN THE DRAWING FILE AS
 471-P-2.19 IS ACTUALLY SHEET P-218. THE ROOF DECK
 DRAINAGE SHEET.
  
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) 2ND REQUEST. THE RESPONSE INDICATES SHEET P6.1 NOTE
 FOR TRAP RESEAL, NOT A TRAP PRIMER. PLEASE REVIEW 2010
 FBC-P
 THE PLANS INDICATE THE USE OF FLOOR DRAINS IN THE
 GARAGE, FIRE PUMP ROOM, DOMESTIC PUMP ROOM AND TREASH
 ROOMS WITH OUT THE USE OF TRAP PRIMER VALVES.
 2010 FBC-P 1002.3 PROHIBITED TRAPS.
 THE FOLLOWING TYPES OF TRAPS ARE PROHIBITED: 1. TRAPS
 THAT DEPEND ON MOVING PARTS TO MAINTAIN THE SEAL.
  
 1002.4 TRAP SEALS.
 EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS
 THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102
 MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO
 ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE
 TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A
 TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR
 ASSE 1044.
  
 6) PLEASE NOTE SHOWER ARE BASED ONTHE TOTAL FLOW RATE
 THROUGH SHOWER HEADS AND BODY SPRAYS A 2 INCH TRAP WILL
 ALLOW FOR 5.7 GPM TO 12.3 GPM PER FBC-P TABLE 709.1. NO
 ACTION IS REQUIRED, JUST INFORMATIONAL.
  
 7) PROJECT DOCS < A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER