Plan Review Notes
Plan Review Notes For Permit 14020547
Permit Number 14020547
Review Stop B
Sequence Number 2
Notes
Date Text
2014-05-01 11:12:54****CORRECTIONS****
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROJECT: LOFTIN PLACE
 CONTRACTOR CONTACT: [email protected]
 ARCHITECT: MSA ARCHITECTS, INC., JOSE I. SAUMELL
 ENGINEER: BBM STRUCTURAL ENGINEERS, JOEL R.
 MIDDLEBROOKS PE
 CONTACT: NEYITA LEIVA, LICENSE & PERMIT SERVICES:
 NEYITALPS01.NET 561-856-6655
  
 1. PROVISO - PER APPLICANT, SCOPE OF THIS FOUNDATION
 PERMIT IS LIMITED TO VIBROCOMPACTION, BELOW GRADE
 FOUNDATIONS, AND WATER, SEWER AND STORM PIPING.
  
 2. PROVISO - PER APPLICANT, PLAT PLAN HAS BEEN
 SUBMITTED.
  
 3-8. OK
  
 9. SEE THRESHOLD PLAN REVIEW - THIS IS REQUIRED PRIOR
 TO PERMIT ISSUANCE PER FLORIDA STATUTE 553.
  
 SHEETS S0.5 AND 0.6 (THRESHOLD INSPECTION PLAN) FROM
 THE BUILDING PERMIT ARE IN REVIEW. PLEASE INCLUDE IN
 THIS PERMIT.
  
 10. PROVISO - FBC 110.7 IMPACT OF CONSTRUCTION. PER
 MANNY GONZALEZ, A POLLUTION PREVENTION PLAN HAS BEEN
 FILED WITH THE ENGINEERING DEPARTMENT.
  
 11. COMMENT FROM REVIEW #1: FBC 110.3.7.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS
 COMPLY WITH THE APPLICABLE FIRE SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND 633 FLORIDA STATUTE.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT THIS IS DULY
 NOTED BUT I WAS UNABLE TO LOCATE THE STATEMENT ON THE
 PLANS (REQUIRED TO BE STATED BY THE ARCHITECT AND BY
 THE ENGINEER).
  
 PLEASE ALSO SEE FLORIDA STATUTE 553.79(7) (D):
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER AND CHAPTER 633.
  
 PLEASE ADVISE AS TO WHICH SHEET THIS STATEMENT CAN BE
 LOCATED, OR ADD TO AT LEAST ONE ARCHITECTURAL AND ONE
 STRUCTURAL SHEET. THIS IS REQUIRED FOR ALL THRESHOLD
 BUILDINGS.
  
 12-13. OK
  
 14. PROVISO - INFORMATIONAL SHEETS NOT RELATED TO
 FOUNDATION HAVE NOT BEEN REVIEWED.
  
 15-16. OK
  
 17. COMMENT FROM REVIEW #1: REVISE PLAN TO INCLUDE WIND
 DESIGN CRITERIA FBC1603.1.4.
  
 RESPONSE IS THAT THIS IS INCLUDED ON THE BUILDING PLAN.
 THE MASTER HAS NOT YET BEEN ISSUED AND IS STILL IN
 REVIEW; THEREFORE IS NOT A PART OF THE PUBLIC
 RECORD/PERMIT DOCUMENT. FOR THIS FOUNDATION PERMIT
 BEING REQUESTED, PLEASE REVISE PLAN TO INCLUDE WIND
 DESIGN CRITERIA AS REQUIRED BY FBC 1603.1.4. IF THE
 STRUCTURAL ENGINEER FEELS THAT WIND DESIGN CRITERIA IS
 NOT RELEVANT TO THE FOUNDATION DESIGN, PLEASE HAVE HIM
 CALL ME TO DISCUSS.
  
 18. COMMENT FROM REVIEW #1: PROVIDE MORE INFORMATION
 FOR THE PILES : TYPE, SIZE, ETC., FBC 107.
 2ND REVIEW, PILES ARE NOT TO BE INSTALLED PER RESPONSE
 LETTER AND PER GEOTECHNICAL REPORT. SEE S5.1, TYPICAL
 CONCRETE COLUMN. THIS DETAIL SHOWS A PILE CAP, PLEASE
 CLARIFY OR REMOVE FROM DETAIL.
  