2014-03-10 16:22:29 | PLUMBING PLAN REVIEW |
| LOFTIN PLACE -FOUNDATION PERMIT |
| PERMIT: 14020547 |
| ADD: 705 N OLIVE AVE |
| CONT: KAST CONSTRUCTION |
| TEL: (561)689-2910 |
| CONTACT: NEYITA (561)856-6655 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: MONDAY MARCH 10/2014 |
| ACTION: DENIED |
| |
| 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 107.3.5 |
| MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| DOCUMENTS: |
| 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.3 PLUMBING |
| SANITARY DRAINAGE |
| VENTS |
| ROOF DRAINAGE |
| SAND INTERCEPTOR OR TRAPS |
| ENVIRONMENTAL REQUIREMENTS |
| PLUMBING RISER |
| |
| 2A) SHEET P-2.1.1.A INDICATES A 8 INCH PIPE FOR GARAGE |
| DRAINAGE TO SAND FILTER SEE CIVIL DWGS, COMPLY WITH |
| 2010 FBC-P 1003.1 WHERE REQUIRED. INTERCEPTORS AND |
| SEPARATORS SHALL BE PROVIDED TO PREVENT THE DISCHARGE |
| OF OIL, GREASE, SAND AND OTHER SUBSTANCES HARMFUL OR |
| HAZARDOUS TO THE BUILDING DRAINAGE SYSTEM, THE PUBLIC |
| SEWER, THE PRIVATE SEWAGE DISPOSAL SYSTEM OR THE SEWAGE |
| TREATMENT PLANT OR PROCESSES. |
| |
| 2B) 1003.11 (IPC 1003.5) SAND INTERCEPTORS IN |
| COMMERCIAL ESTABLISHMENTS. SAND AND SIMILAR |
| INTERCEPTORS FOR HEAVY SOLIDS SHALL BE DESIGNED AND |
| LOCATED SO AS TO BE PROVIDED WITH READY ACCESS FOR |
| CLEANING,AND SHALL HAVE A WATER SEAL OF NOT LESS THAN 6 |
| INCHES (152 MM). |
| |
| 2C) THE PLANS INDICATE PART OF THE GARAGE FLOOR DRAINS |
| (GD) EMPTYING INTO A 8" PIPE TO THE SAND FILTER AND |
| ALSO A 10 INCH THAT EMPTIES INTO A 15 INCH RWL TO |
| STORM? |
| |
| 2D) THIS MAY BE A FOUNDATION PERMIT BUT THE ROOF |
| DRAINAGE IS SIZED FROM THE ROOF AREA AND 1/2 OF THE |
| HEIGHT OF THE PARAET WALLS, THE PLANS ALSO FAIL TO |
| PROVIDE THE CRITERIA FOR SIZING OF THE ROOF DRAINAGE, |
| 2010 FBC-P 1106.1 WITH OUT THIS INFORMATION WE CAN NOT |
| BE SURE THE CONDUCTORS ARE SIZED PROPERLY. 100 YEAR 1 |
| HOUR RAIN FALL 4,5 INCHES. |
| |
| 3) THE SANITARY PLUMBING ISOMETRIC SHEET P-2.1.1.A FOR |
| THE WASHING MACHINES ON THE PLUMBING RISERS IDENTIFIED |
| AS 7, 42 & 50 APPEAR TO HAVE FLIPPED THELABELING OF THE |
| 2" AND 3 " PIPES BACKWARDS THAT WOULD BE REDUCING THE |
| SIZE OF THE VENT FROM 3 INCH TO 2 INCH. |
| |
| 4) THE STRUCTURAL SHEET S-2.0 DETAIL # 6 INDICATES THE |
| USE OF A ELEVATOR PIT AND SUMP, PLEASE PROVIDE |
| COMPLIANCE WITH 2010 FBC-P 1003.4 OIL SEPARATORS |
| REQUIRED. |
| AT REPAIR GARAGES, CAR-WASHING FACILITIES, AT FACTORIES |
| WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND |
| IN HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE |
| INSTALLED INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR |
| FLAMMABLE WASTES SHALL BE DISCHARGED BEFORE EMPTYING |
| INTO THE BUILDING DRAINAGE SYSTEM OR OTHER POINT OF |
| DISPOSAL. |
| |
| EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN |
| HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM |
| IS INSTALLED. |
| |
| 5) THE PLANS INDICATE THE USE OF FLOOR DRAINS IN THE |
| GARAGE, FIRE PUMP ROOM, DOMESTIC PUMP ROOM AND TREASH |
| ROOMS WITH OUT THE USE OF TRAP PRIMER VALVES. 2010 |
| FBC-P |
| 1002.4 TRAP SEALS. |
| EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS |
| THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 |
| MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO |
| ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO |
| LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE |
| INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE |
| TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A |
| TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR |
| ASSE 1044. |
| |
| 6) PLEASE NOTE SHOWER ARE BASED ONTHE TOTAL FLOW RATE |
| THROUGH SHOWER HEADS AND BODY SPRAYS A 2 INCH TRAP WILL |
| ALLOW FOR 5.7 GPM TO 12.3 GPM PER FBC-P TABLE 709.1. NO |
| ACTION IS REQUIRED, JUST INFORMATIONAL. |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |