Plan Review Notes
Plan Review Notes For Permit 14020547
Permit Number 14020547
Review Stop B
Sequence Number 1
Notes
Date Text
2014-03-11 15:13:12****CORRECTIONS****
 ****REVISED 3/14/14****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROJECT: LOFTIN PLACE
 CONTRACTOR CONTACT: [email protected]
 ARCHITECT: MSA ARCHITECTS, INC., JOSE I. SAUMELL
 ENGINEER: BBM STRUCTURAL ENGINEERS, JOEL R.
 MIDDLEBROOKS PE
 CONTACT: NEYITA LEIVA, LICENSE & PERMIT SERVICES:
 NEYITALPS01.NET 561-856-6655
  
  
 1. DEFINE SCOPE OF WORK TO BE INCLUDED ON THIS PERMIT,
 FBC 107. APPLICATION IS FOR FOUNDATION FOR RESIDENTIAL
 AND PARKING STRUCTURES; FOR EXAMPLE, AUGER PILES, ISO
 FOOTINGS, FIRST FLOOR SLAB, WALLS?
  
 2. C02, SCOPE OF WORK SHOWN ON MULTIPLE LOTS AS WELL AS
 A STREET/ALLEY TO BE ABANDONED. HAS THIS PROPERTY BEEN
 REPLATTED, OR HAS A UNITY OF TITLE BEEN FILED? PLEASE
 ADVISE AS TO STATUS.
  
 3. SEPARATE DEMO PERMITS REQUIRED, PLEASE ADVISE AS TO
 STATUS OF DEMO PERMITS.
  
 4. SHEET SD1, TABLES 601 AND 602 APPEAR TO BE THE
 TABLES AND FOOTNOTES FROM FBC 2007 RATHER THAN
 GOVERNING CODE FOR THIS PROJECT, FBC 2010. PLEASE
 REVISE TO CURRENT CODE.
  
 5. SHEET SD1, FIRE SEPARATIONS, APPEARS TO HAVE A TYPO.
 A 1 HOUR REDUCTION FOR OCCUPANCY SEPARATION IS
 INDICATED. ALTHOUGH THIS REDUCTION WAS NOT TAKEN
 (PROVIDED RATING IS 1), PLEASE REMOVE TO AVOID
 CONFUSION OR PROVIDE CODE SECTION WHERE THIS IS
 PERMITTED.
  
 6. SHEET SD1, FIRE SEPARATIONS, TENANT SEPARATION
 OPENING PROTECTION REQUIRED IS 45 MINUTES, FBC TABLE
 715.4, PLEASE REVISE.
  
 7. SHEET SD1, OPENING PROTECTIVES, 3 HOUR REQUIRED FOR
 A 3 HOUR FIRE WALL OR FIRE BARRIER, 90 MINUTE REQUIRED
 FOR 3 HOUR EXTERIOR WALL, FBC TABLE 715.4. PLEASE
 REVISE LANGUAGE IN TABLE TO BE CONSISTENT WITH FBC
 TABLE 715.4.
  
 8. PROVIDE MORE INFORMATION ABOUT PHASE II. WILL PHASE
 II BE DESIGNED TO BE ONE BUILDING WITH PHASE I, OR WILL
 IT BE A SEPARATE BUILDING WITH FIRE RATED SEPARATIONS?
 WHAT IS THE PROPOSED HEIGHT AND AREA OF PHASE II,
 HIGHEST HABITABLE FLOOR AND ROOF HEIGHT? FBC 107, FBC
 CHAPTER 5.
  
 9. FS553.79, FBC 110.3.7, SPECIAL INSPECTOR REQUIRED
 FOR THIS THRESHOLD BUILDING. A COPY OF THE SPECIAL
 INSPECTOR AGREEMENT AND PROGRAM INFORMATION HAS BEEN
 EMAILED TO [email protected].
  
 10. FBC 110.7 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT GRANTED BY
 THE APPLICABLE PROPERTY OWNER, UNDER TERMS OR
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES, BUT IS NOT
 LIMITED TO, THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFFS, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL
 NOT ADVERSELY IMPACT LEGAL HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, AND MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE DRAINAGE
 PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY
 PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE
 DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION,
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A
 LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE
 INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 11. FBC 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 12. SEE FBC CHAPTER 33, SAFEGUARDS DURING CONSTRUCTION;
 PLEASE NOTE ON PLAN.
  
 13. PROVIDE THE SOILS INVESTIGATION REPORT PREPARED BY
 ARDAMAN & ASSOCIATES DATED OCTOBER 22, 2013 (REFERENCE
 ON SHEET S5.2), FBC 1803.
  
 14. ADVISORY ONLY; INFORMATIONAL SHEETS NOT RELATED TO
 FOUNDATION HAVE NOT BEEN REVIEWED (FLOOR PLAN,
 ELEVATIONS).
  
 15. INFORMATIONAL ONLY: IMPACT FEE ASSESSMENT BY PALM
 BEACH COUNTY REQUIRED PRIOR TO BUILDING PERMIT
 ISSUANCE. SEE IMPACT FEE REVIEW (NOT REQUIRED AT THIS
 TIME FOR FOUNDATION PERMIT).
  
 16. INDEX REFERS TO S0.1, UNABLE TO LOCATE, FBC 107.
  
 17. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA
 FBC1603.1.4.
  
 18. PROVIDE MORE INFORMATION FOR THE PILES - TYPE,
 SIZE, ETC., FBC 107.
  
  
  
  