2014-03-11 15:13:12 | ****CORRECTIONS**** |
| ****REVISED 3/14/14**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| PROJECT: LOFTIN PLACE |
| CONTRACTOR CONTACT: [email protected] |
| ARCHITECT: MSA ARCHITECTS, INC., JOSE I. SAUMELL |
| ENGINEER: BBM STRUCTURAL ENGINEERS, JOEL R. |
| MIDDLEBROOKS PE |
| CONTACT: NEYITA LEIVA, LICENSE & PERMIT SERVICES: |
| NEYITALPS01.NET 561-856-6655 |
| |
| |
| 1. DEFINE SCOPE OF WORK TO BE INCLUDED ON THIS PERMIT, |
| FBC 107. APPLICATION IS FOR FOUNDATION FOR RESIDENTIAL |
| AND PARKING STRUCTURES; FOR EXAMPLE, AUGER PILES, ISO |
| FOOTINGS, FIRST FLOOR SLAB, WALLS? |
| |
| 2. C02, SCOPE OF WORK SHOWN ON MULTIPLE LOTS AS WELL AS |
| A STREET/ALLEY TO BE ABANDONED. HAS THIS PROPERTY BEEN |
| REPLATTED, OR HAS A UNITY OF TITLE BEEN FILED? PLEASE |
| ADVISE AS TO STATUS. |
| |
| 3. SEPARATE DEMO PERMITS REQUIRED, PLEASE ADVISE AS TO |
| STATUS OF DEMO PERMITS. |
| |
| 4. SHEET SD1, TABLES 601 AND 602 APPEAR TO BE THE |
| TABLES AND FOOTNOTES FROM FBC 2007 RATHER THAN |
| GOVERNING CODE FOR THIS PROJECT, FBC 2010. PLEASE |
| REVISE TO CURRENT CODE. |
| |
| 5. SHEET SD1, FIRE SEPARATIONS, APPEARS TO HAVE A TYPO. |
| A 1 HOUR REDUCTION FOR OCCUPANCY SEPARATION IS |
| INDICATED. ALTHOUGH THIS REDUCTION WAS NOT TAKEN |
| (PROVIDED RATING IS 1), PLEASE REMOVE TO AVOID |
| CONFUSION OR PROVIDE CODE SECTION WHERE THIS IS |
| PERMITTED. |
| |
| 6. SHEET SD1, FIRE SEPARATIONS, TENANT SEPARATION |
| OPENING PROTECTION REQUIRED IS 45 MINUTES, FBC TABLE |
| 715.4, PLEASE REVISE. |
| |
| 7. SHEET SD1, OPENING PROTECTIVES, 3 HOUR REQUIRED FOR |
| A 3 HOUR FIRE WALL OR FIRE BARRIER, 90 MINUTE REQUIRED |
| FOR 3 HOUR EXTERIOR WALL, FBC TABLE 715.4. PLEASE |
| REVISE LANGUAGE IN TABLE TO BE CONSISTENT WITH FBC |
| TABLE 715.4. |
| |
| 8. PROVIDE MORE INFORMATION ABOUT PHASE II. WILL PHASE |
| II BE DESIGNED TO BE ONE BUILDING WITH PHASE I, OR WILL |
| IT BE A SEPARATE BUILDING WITH FIRE RATED SEPARATIONS? |
| WHAT IS THE PROPOSED HEIGHT AND AREA OF PHASE II, |
| HIGHEST HABITABLE FLOOR AND ROOF HEIGHT? FBC 107, FBC |
| CHAPTER 5. |
| |
| 9. FS553.79, FBC 110.3.7, SPECIAL INSPECTOR REQUIRED |
| FOR THIS THRESHOLD BUILDING. A COPY OF THE SPECIAL |
| INSPECTOR AGREEMENT AND PROGRAM INFORMATION HAS BEEN |
| EMAILED TO [email protected]. |
| |
| 10. FBC 110.7 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| AFFECT SAID PROPERTY PURSUANT TO A CONSENT GRANTED BY |
| THE APPLICABLE PROPERTY OWNER, UNDER TERMS OR |
| CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| THIS INCLUDES, BUT IS NOT |
| LIMITED TO, THE CONTROL OF DUST, NOISE, WATER OR |
| DRAINAGE RUN-OFFS, DEBRIS, AND THE STORAGE OF |
| CONSTRUCTION MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL |
| NOT ADVERSELY IMPACT LEGAL HISTORIC SURFACE WATER |
| DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, AND MAY |
| REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE POSITIVE DRAINAGE |
| PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| DEVELOPERS, CONTRACTORS AND OWNERS OF ALL NEW |
| RESIDENTIAL DEVELOPMENT, INCLUDING |
| ADDITIONS, POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR |
| ITEMS, ON EXISTING PROPERTIES RESULTING IN A |
| SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY |
| PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE |
| DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION, |
| PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY |
| INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON |
| COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A |
| LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE |
| INSPECTOR IN ORDER TO RECEIVE |
| APPROVAL OF THE FINAL INSPECTION. |
| |
| 11. FBC 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 12. SEE FBC CHAPTER 33, SAFEGUARDS DURING CONSTRUCTION; |
| PLEASE NOTE ON PLAN. |
| |
| 13. PROVIDE THE SOILS INVESTIGATION REPORT PREPARED BY |
| ARDAMAN & ASSOCIATES DATED OCTOBER 22, 2013 (REFERENCE |
| ON SHEET S5.2), FBC 1803. |
| |
| 14. ADVISORY ONLY; INFORMATIONAL SHEETS NOT RELATED TO |
| FOUNDATION HAVE NOT BEEN REVIEWED (FLOOR PLAN, |
| ELEVATIONS). |
| |
| 15. INFORMATIONAL ONLY: IMPACT FEE ASSESSMENT BY PALM |
| BEACH COUNTY REQUIRED PRIOR TO BUILDING PERMIT |
| ISSUANCE. SEE IMPACT FEE REVIEW (NOT REQUIRED AT THIS |
| TIME FOR FOUNDATION PERMIT). |
| |
| 16. INDEX REFERS TO S0.1, UNABLE TO LOCATE, FBC 107. |
| |
| 17. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA |
| FBC1603.1.4. |
| |
| 18. PROVIDE MORE INFORMATION FOR THE PILES - TYPE, |
| SIZE, ETC., FBC 107. |
| |
| |
| |
| |