2014-02-13 19:05:06THE FOLLOWING CORRECTIONS SHALL BE MADE TO THE DRAWINGS
 FOR APPROVAL:
 1. AS PER FBC-B SECTION 907.1.2, THE SHOP DRAWINGS
 SHALL INDICATE THE LOCATION OF THE FIRE ALARM CONTROL
 UNIT AND NOTIFICATION POWER SUPPLIES. VOLTAGE DROP
 CALCULATIONS AND THE USE OF ALL ROOMS.
 IN ADDITION TO THE ABOVE, THERE IS A CONFLICT BETWEEN
 THE SCOPE OF WORK AS MENTIONED ON THE PLANS, THE PERMIT
 APPLICATION AND THE DATA PROVIDED. UNDER THE
 CIRCUMSTANCES, I BELIEVE THAT ALL YOU WILL BE DOING IS
 ADDING A POWER SUPPLY TO OPERATE THE NEW NOTIFICATION
 DEVICES, AS I DON'T SEE ANY INITIATION DEVICES ON THE
 PLANS.
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  