2014-02-15 08:55:242010 FBC
  
 DENIED BY BUILDING
  
 1) NOT ENOUGH INFORMATION WAS SUBMITTED TO DETERMINE
 THAT THE INSTALLATION OF THE ROOF SYSTEM WILL BE CODE
 COMPLIANT. CITY AMENDMENTS 107.2.1 AND FBC 1609.1
  
 2) THE DESCRIPTION OF WORK ON THE APPLICATION SPECIFIES
 RECOVERING OF EXISTING FLAT ROOF. HOWEVER, THE
 MIAMI-DADE NOA #12-1003.05 THAT WAS SUBMITTED IS FOR A
 NEW ROOF OR A TEAR OFF OF THE EXISTING ROOFING. PLEASE
 CLARIFY. CITY AMENDMENTS 107.2.1
  
 3) THE MEAN ROOF HEIGHT OF THE STRUCTURE IS REQUIRED IN
 ORDER TO DETERMINE THE REQUIRED UPLIFT PRESSURES. FBC
 1609.1.1
  
 4) SPECIFY WHICH ONE OF THE APPROVED AND TESTED
 ASSEMBLIES AND FASTENING OPTIONS LISTED IN THE PRODUCT
 APPROVAL YOU ARE PROPOSING TO INSTALL. CITY AMENDMENTS
 107.2.1
  
 5) THIS PROJECT IS LOCATED IN A 170 MPH VULT WIND SPEED
 AND EXPOSURE CATEGORY C. THE HIGHEST MAXIMUM DESIGN
 PRESSURE LISTED IN THE NOA IS -60 PSF, WHICH IS NOT
 ENOUGH FOR THE CORNER AND PERIMETER AREAS. SUBMIT TWO
 SETS OF ORIGNAL SIGNED AND SEALED RAS 117 CALCULATIONS
 FOR ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER
 7 OF THE NOA. FBC 1609.1
  