Plan Review Notes For Permit 14020497 |
Permit Number |
14020497 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-04-16 14:33:43 | APPROVED AS NOTED ON THE APPROVED PLANS: | | 1. AS PER NEC 210.52(A)2 THERE IS A MISSING FLOOR | | OUTLET ALONG THE STAIR RAIL ON THE 2ND FLOOR. | | 2. AN OUTLET ALONG THE OUTSIDE WALL MAY HAVE TO BE | | RELOCATED AS MARKED FOR LINEAR FLOOR AREA COMPLIANCE. | | 3. SERVICE RISER FAILED TO MENTION THE GROUNDED | | CONDUCTOR INSIDE THE SUB-FEEDS, A NOTE WAS ADDED WITH | | SPECIFIC REQUIREMENTS (THIS WILL NEED AN (EGC) | | EQUIPMENT GROUNDING CONDUCTOR PER TABLE NEC 250.122, | | UNLESS METAL CONDUIT IS USED.) WAS ADDED TO THE RISER | | DIAGRAMS. |
|