Plan Review Notes
Plan Review Notes For Permit 14020497
Permit Number 14020497
Review Stop B
Sequence Number 2
Notes
Date Text
2014-05-01 18:04:462010 FBC
  
 DENIED BY BUILDING
  
 1) SHOW COMPLIANCE WITH FBC R318.6 WHICH REQUIRES
 GUTTERS WITH DOWNSPOUTS ON ALL BUILDINGS WITH EAVES OF
 LESS THAN 6 INCH HORIZONTAL PROJECTION. GUTTERS ARE
 REQUIRED ANYWHERE THE ROOF IS SLOPED TO DRAIN THE WATER
 FROM THE ROOF AND THE EAVES OVERHANG LESS THAN 6
 INCHES.
  
 2) SHEET S-1 HAS BASE SHEET ENHANCED FASTENING
 CALCULATIONS FOR GAF MODIFIED ROOFING NOA NUMBER
 12-1003.05. PLEASE SUBMIT TWO COPIES OF THE PRODUCT
 APPROVALS THAT HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD. DCA RULE 9N-3
  
 3) THE BASE SHEET ENHANCED FASTENING CALCULATIONS ON
 SHEET S-1 STATE THEY ARE FOR A ROOF HEIGHT OF LESS THAN
 15'. THE PLANS SHOW THAT THE ROOF HEIGHT IS MORE THAN
 20'. PLEASE REVISE TO SHOW ROOF HEIGHT OF LESS THAN
 25'. FBC R301.2.1
  
 4) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 CONNECTORS, HANGERS AND ANCHORS SHOWN ON THE PLANS OR
 SPECIFY THE PRODUCT APPROVAL NUMBER FOR EACH ON THE
 PLANS. DCA RULE 9N-3 THE ONE THAT WAS SUBMITTED DID NOT
 INCLUDE THE SIMPSON LUS210, HM9KT, ABU66 AND BCS2-3/6
 CONNECTORS.
  
 5) THE PLANS SHOW BARREL TILE ON THE COVERED PATIO
 ROOF. SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 ROOF TILE THAT WILL BE USED. SPECIFY HOW IT WILL BE
 ATTACHED TO RESIST OVERTURNING MOMENT BY MARKING ONE OF
 THE FASTENING OPTIONS ON THE PRODUCT APPROVAL. IF
 ADHESIVES ARE TO BE USED FOR TILE INSTALLATION, SUBMIT
 TWO C0PIES OF ITS PRODUCT APPROVALS AS REQUIRED BY DCA
 RULE 9N-3.
  
 6) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 7) THE PRODUCT APPROVAL INSTALLATION DRAWINGS FOR THE
 FRENCH DOORS AND LAWSON SINGLE HUNG WINDOWS WERE NOT
 SHRUNK TO FIT ON 8.5" X 11" PAPER WHEN THEY WERE
 PRINTED. THIS CAUSED SOME OF THE REQUIRED INFORMATION
 TO BE MISSING FROM THE DRAWINGS. SUBMIT COMPLETE
 INSTALLATION DRAWINGS. DCA RULE 9N-3
  
 8) IN ORDER TO SPEED THE PLAN REVIEW PROCESS, PLEASE
 SUBMIT A RESPONSE LETTER WITH THE RE-SUBMITTAL
 INDICATING HOW EACH OF THE REVIEW COMMENTS WAS
 ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]