2014-03-04 17:15:28 | FIRST ELECTRICAL REVIEW FAILED AS NOTED BELOW; |
| 1. NEC 210.52 HAS SPECIFIC REQUIREMENTS FOR OUTLET |
| PLACEMENTS IN DWELLING UNITS WHICH ARE NOT FOLLOWED ON |
| THE SUBMITTED DRAWING. BESIDES THE MISSING OUTLETS OF |
| THE BALCONY, THE FRONT AND REAR OF THE RESIDENCE, YOU |
| MUST ADHERE TO THE 6-2-12 RULE: AN OUTLET WITHIN 6' OF |
| EVERY DOOR. EVERY WALL GREATER THAN 2' SHALL HAVE AN |
| OUTLET. THERE CAN BE NO MORE THAN 12 LINEAR FT ALONG |
| THE WALL BETWEEN OUTLETS. |
| 2. NEC 300.5(B) DESIGNATE THE INTERIOR OF UNDERGROUND |
| RACEWAYS AS WET LOCATIONS, THEREFORE THE INSULATION OF |
| THE FEEDER CONDUCTORS SHALL BE LISTED ACCORDINGLY. |
| 3. MARK ON THE FLOOR PLAN THE LOCATION OF BOTH, THE |
| ELECTRIC SERVICE METER AND THE ELECTRICAL PANEL. |
| 4. NEC 210.12 HAS BROADER ARC-FAULT REQUIREMENTS THAN |
| REFLECTED ON YOUR PANEL SCHEDULE. |
| 5. NEC 406.8 REQUIRES THAT ALL OUTSIDE OUTLETS BE |
| LISTED "WR" WEATHER RESISTANT AND BE UNDER AN IN-USE |
| TYPE COVER. |
| 6. NEC 406.11 REQUIRES THAT OUTLETS IN DWELLING UNITS |
| BE LISTED "TR" TAMPER-RESISTANT. |
| 7. THERE IS A CONFLICT BETWEEN YOUR ELECTRICAL NOTE #13 |
| AND THE PANEL SCHEDULE CIRCUIT 23. THE ELECTRICAL NOTE |
| SHALL PREVAIL. THE SMOKE DETECTORS SHOULD BE ON A |
| LIGHTING CIRCUIT RATHER THAN ON A DEDICATED CIRCUIT. |
| 8. AS PER THE FBC-ENERGY CONSERVATION, AT LEAST 50% OF |
| YOUR LAMPS SHALL BE OF THE ENERGY EFFICIENT TYPE |
| 9. THE INSTALLATION OF THE AIR HANDLER IN THE ATTIC |
| CREATES CONFLICTS WITH THE FBC-ENERGY SECTION 402, |
| BUILDING THERMAL ENVELOP, AND FURTHER REQUIRES |
| ADDITIONAL ITEMS, SUCH AS A PERMANENT LADDER TO THE |
| ATTIC BY THE NEC |
| THE FOLLOWING ARE RECOMMENDATIONS: |
| 1. RELOCATE THE LIVING ROOM SMOKE DETECTOR AWAY FROM |
| THE KITCHEN AND CLOSER TO THE STAIRS. |
| 2. THE CEILING FANS WITH A LIGHT KIT SHOULD HAVE A |
| SECOND SWITCH LEG TO INDEPENDENTLY CONTROL EACH |
| FUNCTION. |
| 3. CHECK YOUR ELECTRICAL NOTES FOR CONFLICTING DATA AND |
| REDUNDANCY. |
| FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE |
| CONTACT: |
| MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 |