Plan Review Notes
Plan Review Notes For Permit 14020497
Permit Number 14020497
Review Stop E
Sequence Number 1
Notes
Date Text
2014-03-04 17:15:28FIRST ELECTRICAL REVIEW FAILED AS NOTED BELOW;
 1. NEC 210.52 HAS SPECIFIC REQUIREMENTS FOR OUTLET
 PLACEMENTS IN DWELLING UNITS WHICH ARE NOT FOLLOWED ON
 THE SUBMITTED DRAWING. BESIDES THE MISSING OUTLETS OF
 THE BALCONY, THE FRONT AND REAR OF THE RESIDENCE, YOU
 MUST ADHERE TO THE 6-2-12 RULE: AN OUTLET WITHIN 6' OF
 EVERY DOOR. EVERY WALL GREATER THAN 2' SHALL HAVE AN
 OUTLET. THERE CAN BE NO MORE THAN 12 LINEAR FT ALONG
 THE WALL BETWEEN OUTLETS.
 2. NEC 300.5(B) DESIGNATE THE INTERIOR OF UNDERGROUND
 RACEWAYS AS WET LOCATIONS, THEREFORE THE INSULATION OF
 THE FEEDER CONDUCTORS SHALL BE LISTED ACCORDINGLY.
 3. MARK ON THE FLOOR PLAN THE LOCATION OF BOTH, THE
 ELECTRIC SERVICE METER AND THE ELECTRICAL PANEL.
 4. NEC 210.12 HAS BROADER ARC-FAULT REQUIREMENTS THAN
 REFLECTED ON YOUR PANEL SCHEDULE.
 5. NEC 406.8 REQUIRES THAT ALL OUTSIDE OUTLETS BE
 LISTED "WR" WEATHER RESISTANT AND BE UNDER AN IN-USE
 TYPE COVER.
 6. NEC 406.11 REQUIRES THAT OUTLETS IN DWELLING UNITS
 BE LISTED "TR" TAMPER-RESISTANT.
 7. THERE IS A CONFLICT BETWEEN YOUR ELECTRICAL NOTE #13
 AND THE PANEL SCHEDULE CIRCUIT 23. THE ELECTRICAL NOTE
 SHALL PREVAIL. THE SMOKE DETECTORS SHOULD BE ON A
 LIGHTING CIRCUIT RATHER THAN ON A DEDICATED CIRCUIT.
 8. AS PER THE FBC-ENERGY CONSERVATION, AT LEAST 50% OF
 YOUR LAMPS SHALL BE OF THE ENERGY EFFICIENT TYPE
 9. THE INSTALLATION OF THE AIR HANDLER IN THE ATTIC
 CREATES CONFLICTS WITH THE FBC-ENERGY SECTION 402,
 BUILDING THERMAL ENVELOP, AND FURTHER REQUIRES
 ADDITIONAL ITEMS, SUCH AS A PERMANENT LADDER TO THE
 ATTIC BY THE NEC
 THE FOLLOWING ARE RECOMMENDATIONS:
 1. RELOCATE THE LIVING ROOM SMOKE DETECTOR AWAY FROM
 THE KITCHEN AND CLOSER TO THE STAIRS.
 2. THE CEILING FANS WITH A LIGHT KIT SHOULD HAVE A
 SECOND SWITCH LEG TO INDEPENDENTLY CONTROL EACH
 FUNCTION.
 3. CHECK YOUR ELECTRICAL NOTES FOR CONFLICTING DATA AND
 REDUNDANCY.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  
  
  