Date |
Text |
2014-03-18 14:29:32 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) SUBMIT TO COPIES OF A SURFACE WATER DRAINAGE PLAN |
| SHOWING COMPLIANCE WITH FBC R401.3. |
| |
| 2) SHOW THAT THE FOOTING FOR THE STRUCTURE IS A MINIMUM |
| OF 12" BELOW GRADE AS REQUIRED BY FBC R403.1.4. |
| |
| 3) SHOW COMPLIANCE WITH SECTION R318 FOR PROTECTION |
| AGAINST TERMITES. ON SHEET S-1 TERMITE PROTECTION IS |
| ONLY SPECIFIED FOR THE PORCH SLAB. |
| |
| 4) SHOW COMPLIANCE WITH FBC R318.6 WHICH REQUIRES |
| GUTTERS WITH DOWNSPOUTS ON ALL BUILDINGS WITH EAVES OF |
| LESS THAN 6 INCH HORIZONTAL PROJECTION. |
| |
| 5) SHEET S-1 HAS BASE SHEET ENHANCED FASTENING |
| CALCULATIONS FOR EXPIRED NOA NUMBER 09-0224.01. PLEASE |
| REMOVE THEM. |
| |
| 6) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| CONNECTORS, HANGERS AND ANCHORS SHOWN ON THE PLANS OR |
| SPECIFY THE PRODUCT APPROVAL NUMBER FOR EACH ON THE |
| PLANS. DCA RULE 9N-3 |
| |
| 7) THE PLANS SHOW BARREL TILE ON THE COVERED PATIO |
| ROOF. HOWEVER, PRODUCT APPROVALS WERE SUBMITTED FOR GAF |
| ASPHALT SHINGLES (NOA NO. 11-112-04) WHICH HAS BEEN |
| SUPERSEDED. PLEASE CLARIFY AND SUBMIT CURRENT PRODUCT |
| APPROVALS. IF BARREL TILE IS TO BE USED SPECIFY HOW IT |
| WILL BE ATTACHED TO RESIST OVERTURNING MOMENT. IF |
| ADHESIVES ARE TO BE USED FOR TILE INSTALLATION, SUBMIT |
| TWO C0PIES OF ITS PRODUCT APPROVALS AS REQUIRED BY DCA |
| RULE 9N-3. |
| |
| 8) PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| AMENDMENTS 107.3.4.1 |
| |
| 9) THE PRODUCT APPROVAL FOR THE TPO ROOFING WAS NOT |
| APPROVED IN WRITING BY THE DESIGNER. IT IS FOR STEEL |
| DECK APPLICATION AND THE PLANS SPECIFY A WOOD DECK. |
| PLEASE CORRECT. CITY AMENDMENTS 107.2.1 |
| |
| 10) THE FRENCH DOOR PRODUCT APPROVAL THAT WAS SUBMITTED |
| IS NON-IMPACT RATED. STORM PANELS ARE REQUIRED. SUBMIT |
| TWO COPIES OF PRODUCT APPROVALS FOR THE STORM PANELS |
| WITH AN INSTALLATION SCHEDULE AND A KEY PLAN. DCA RULE |
| 9N-3 |
| |
| 11) THE REQUIRED EGRESS DOOR (FRONT DOOR) IS NOT |
| ALLOWED TO BE SHUTTERED. SUBMIT PRODUCT APPROVALS FOR A |
| LARGE MISSILE IMPACT RATED DOOR. FBC R311.2 |
| |
| 12) THE PRODUCT APPROVALS FOR THE LARGE MISSILE IMPACT |
| RATED LAWSON WINDOWS IS EXPIRED. SUBMIT CURRENT PRODUCT |
| APPROVALS. DCA RULE 9N-3. |
| |
| 13) IN ORDER TO SPEED THE PLAN REVIEW PROCESS, PLEASE |
| SUBMIT A RESPONSE LETTER WITH THE RE-SUBMITTAL |
| INDICATING HOW EACH OF THE REVIEW COMMENTS WAS |
| ADDRESSED. |
| |