2014-02-27 11:16:10JEFFERSON APARTMENTS
 FIRE ALARM SYSTEM
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE SIZE, TYPE AND BURIAL DEPTH OF ALL CONDUITS.
 NEC 300.5
 PROVIDE SPECIFICATIONS AND LISTING ON WIRING METHODS.
 NOTE THAT ALL WIRING METHODS LOCATED BELOW GRADE MUST
 BE LISTED FOR WET LOCATION. NEC 110.11, 760.3
 PROVIDE A GROUNDING AND BONDING DETAIL FOR THE SURGE
 PROTECTORS. NEC 285.21, 285.26
 PROVIDE VERIFICATION THAT A LISTED PRIMARY PROTECTOR
 HAS BEEN PROVIDED AT EACH END OF THE INTER BUILDING
 CIRCUITS. NEC 760.32, 800.90
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
  