Plan Review Notes For Permit 14020410 |
Permit Number |
14020410 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-02-27 11:10:25 | JEFFERSON APARTMENTS | | FIRE ALARM SYSTEM | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | INDICATE SIZE, TYPE AND BURIAL DEPTH OF ALL CONDUITS. | | NEC 300.5 | | PROVIDE SPECIFICATIONS AND LISTING ON WIRING METHODS. | | NOTE THAT ALL WIRING METHODS LOCATED BELOW GRADE MUST | | BE LISTED FOR WET LOCATION. NEC 110.11, 760.3 | | PROVIDE A GROUNDING AND BONDING DETAIL FOR THE SURGE | | PROTECTORS. NEC 285.21, 285.26 | | PROVIDE VERIFICATION THAT A LISTED PRIMARY PROTECTOR | | HAS BEEN PROVIDED AT EACH END OF THE INTER BUILDING | | CIRCUITS. NEC 760.32, 800.90 | | | | ROBERT LECKY, CBO | | ELECTRICAL PLANS REVIEW | | |
|