2014-02-26 18:41:39 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| AND ARE TO INCLUDE ALL INFORMATION FOR THE ENGINEER |
| REQUIRED BY FAC61G15-23.002. IT IS NOT CLEAR WHICH OF |
| THE VARIOUS COMPANY NAMES AND ADDRESSES ON THE PLAN ARE |
| FOR THE ENGINEER. NO CERTIFICATE OF AUTHORIZATION |
| NUMBER PROVIDED, AND THE ADDRESSES ON THE PLAN DO NOT |
| MATCH DBPR RECORDS FOR THIS ENGINEER. PLEASE INCLUDE. |
| |
| 2. FBC 107: |
| |
| ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5). |
| |
| MANY SHEETS ARE NOT SIGNED AND SEALED AND ARE MARKED |
| "INFORMATIONAL." SOME SHEETS HAVE FASTENING |
| SPECIFICATIONS, SO THIS IS A DESIGN, NOT |
| "INFORMATIONAL". PLEASE HAVE THE STRUCTURAL ENGINEER |
| SIGN AND SEAL ANY SHEETS WITH STRUCTURAL |
| SPECIFICATIONS. FOR EXAMPLE, A11, ITEM 5. |
| |
| 3. FASTENING SPECIFICATIONS FOR ALL COMPONENTS REQUIRED |
| TO BE COMPLETE - NUMBER OF FASTENERS, TYPE OF FASTENER, |
| DIAMETER, MINIMUM EMBEDMENT IF APPLICABLE. FBC 1609. |
| |
| 4. WIND DESIGN CRITERIA REQUIRED TO BE ON THE PLAN, FBC |
| 1603.1.4. |
| |
| 5. SOME SHEETS ARE NOT LEGIBLE; FOR INSTANCE, DETAIL 6 |
| ON SHEET A4. PRIOR TO RESUBMITTAL, CONFIRM THAT ALL |
| INFORMATION ON THE PLANS ARE LEGIBLE. IF THE |
| INFORMATION IS NOT REQUIRED, REMOVE FROM THE PLAN, FBC |
| 107. |
| |
| 6. CABINETS ARE SHOWN AS PROPOSED. PROVIDE DCA APPROVAL |
| OR ENGINEERING FOR CABINETS, FBC 1609. |
| |
| |