2014-02-20 11:16:38MECHANICAL REVIEW SECOND CHECKLIST.
 CODE: 2010 FBC.
  
  
 ***ORIGINAL COMMENT:
 1- PROVIDE 2 COMPLETE SITE SPECIFIC ENGINEERING
 DRAWINGS FOR THE A/C STANDS. SEC. 301.12 OF 2010
 FBC-MECHANICAL.
  
 ***ENGINEERING INFORMATION SUBMITTED FROM "ENGINEERING
 EXPRESS" NEED TO HAVE ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
 IN ADDITION, ENGINEERING EXPRESS PACKAGE SUBMITTED
 REQUIRES SITE SPECIFIC ENGINEERING.
  
 ***RESPONSE TO SUBMITTAL:
 ENGINEERING INFORMATION SUBMITTED IS NOT SITE SPECIFIC.
 IT'S GENERIC INFORMATION. ENGINEER NEEDS TO PROVIDE
 COMPLETE INFORMATION FOR THIS SPECIFIC BUILDING.
  
  