Plan Review Notes For Permit 14020277 |
Permit Number |
14020277 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-02-10 17:10:18 | MECHANICAL REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE 2 COMPLETE SITE SPECIFIC ENGINEERING | | DRAWINGS FOR THE A/C STANDS. SEC. 301.12 OF 2010 | | FBC-MECHANICAL. | | | | ***ENGINEERING INFORMATION SUBMITTED FROM "ENGINEERING | | EXPRESS" NEED TO HAVE ENGINEER'S ORIGINAL SEAL AND | | SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE. | | IN ADDITION, ENGINEERING EXPRESS PACKAGE SUBMITTED | | REQUIRES SITE SPECIFIC ENGINEERING. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|