2014-08-19 15:10:52****CORRECTIONS****
 REVIEW #4
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 ON 8/19, A SURVEY WAS SUBMITTED, WITH DESCRIPTION:
 "CORRECTIONS TO SURVEY OF EXPANSION." IT IS UNCLEAR WHY
 THIS WAS SUBMITTED AS COMMENTS WERE NOT ADDRESSED. FOR
 YOUR CONVENIENCE, COMMENTS FROM REVIEWS #2 & #3 ARE
 BELOW. IN THE FUTURE, INCLUDE A RESPONSE LETTER STATING
 HOW EACH ITEM WAS ADDRESSED.
  
  
  
 COMMENT FROM PREVIOUS LISTS:
  
 1. AN APPLICATION FOR RELOCATION OF EXISTING SITE
 LIGHTING WAS SUBMITTED. NO STRUCTURAL PLAN WAS
 PROVIDED, FBC 107. THIS SHOULD INCLUDE A STRUCTURAL
 DETAIL FOR THE PROPOSED INSTALLATION AND WIND DESIGN
 CRITERIA FBC1603.1.4.
  
 INFORMATION REGARDING THE ORIGINAL INSTALLATION CAN BE
 FOUND ON SHEET E2.1 (AND OTHER SHEETS) IN THE PLANS FOR
 06090691. IF YOU NEED ACCESS TO THESE (OR OTHER) PLANS,
 PLEASE CONTACT [email protected] OR [email protected]
 (RECORDS RESEARCH REQUEST).
  
 3RD REVIEW:
  
 DOCUMENTS SUBMITTED ARE CONFUSING.
  
 ELECTRICAL ENGINEER STATES ON SHEET E5.1: "DETAIL WAS
 RECOVERED FROM INITIAL BUILDING PROJECT. ALL EXISTING
 STRUCTURAL CALCULATIONS SHOULD STILL APPLY." THE
 ORIGINAL BUILDING WAS DESIGNED
  
 STRUCTURAL ENGINEER STATES IN A LETTER: "THE DESIGN
 WIND CRITERIA FOR THE FACILITY IS AS FOLLOWS: 1. DESIGN
 WIND SPEED 170MPH. 2. WIND EXPOSURE CATEGORY: C."
  
 ORIGINAL BUILDING WAS DESIGNED AS EXPOSURE B (SEE SHEET
 S2.1 OF ORIGINAL BUILDING PLAN). THE DEFINITION OF
 EXPOSURES B AND C HAVE CHANGED SINCE FBC 2004. THE
 STRUCTURAL ENGINEER DOES NOT REFER TO THE LIGHT POLE OR
 LIGHT POLE FIXTURES, AND DOES NOT REFER TO SHEET E5,
 NOR IS THERE ANY INDICATION THAT HE HAS REVIEWED THAT
 DETAIL. ASSUMPTION THAT THE PREVIOUS INSTALLATION
 COMPLIES WITH CURRENT CODE IS NOT NECESSARILY A CORRECT
 ASSUMPTION.
  
 PROVIDE CALCULATIONS FOR PROPOSED RELOCATION OF LIGHT
 POLE AND FOR PROPOSED RELOCATED (OR NEW) FIXTURES, FBC
 1609.