2014-08-16 16:31:10 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| COMMENT FROM PREVIOUS LIST: |
| |
| 1. AN APPLICATION FOR RELOCATION OF EXISTING SITE |
| LIGHTING WAS SUBMITTED. NO STRUCTURAL PLAN WAS |
| PROVIDED, FBC 107. THIS SHOULD INCLUDE A STRUCTURAL |
| DETAIL FOR THE PROPOSED INSTALLATION AND WIND DESIGN |
| CRITERIA FBC1603.1.4. |
| |
| INFORMATION REGARDING THE ORIGINAL INSTALLATION CAN BE |
| FOUND ON SHEET E2.1 (AND OTHER SHEETS) IN THE PLANS FOR |
| 06090691. IF YOU NEED ACCESS TO THESE (OR OTHER) PLANS, |
| PLEASE CONTACT [email protected] OR [email protected] |
| (RECORDS RESEARCH REQUEST). |
| |
| 3RD REVIEW: |
| |
| DOCUMENTS SUBMITTED ARE CONFUSING. |
| |
| ELECTRICAL ENGINEER STATES ON SHEET E5.1: "DETAIL WAS |
| RECOVERED FROM INITIAL BUILDING PROJECT. ALL EXISTING |
| STRUCTURAL CALCULATIONS SHOULD STILL APPLY." THE |
| ORIGINAL BUILDING WAS DESIGNED |
| |
| STRUCTURAL ENGINEER STATES IN A LETTER: "THE DESIGN |
| WIND CRITERIA FOR THE FACILITY IS AS FOLLOWS: 1. DESIGN |
| WIND SPEED 170MPH. 2. WIND EXPOSURE CATEGORY: C." |
| |
| ORIGINAL BUILDING WAS DESIGNED AS EXPOSURE B (SEE SHEET |
| S2.1 OF ORIGINAL BUILDING PLAN). THE DEFINITION OF |
| EXPOSURES B AND C HAVE CHANGED SINCE FBC 2004. THE |
| STRUCTURAL ENGINEER DOES NOT REFER TO THE LIGHT POLE OR |
| LIGHT POLE FIXTURES, AND DOES NOT REFER TO SHEET E5, |
| NOR IS THERE ANY INDICATION THAT HE HAS REVIEWED THAT |
| DETAIL. ASSUMPTION THAT THE PREVIOUS INSTALLATION |
| COMPLIES WITH CURRENT CODE IS NOT NECESSARILY A CORRECT |
| ASSUMPTION. |
| |
| PROVIDE CALCULATIONS FOR PROPOSED RELOCATION OF LIGHT |
| POLE AND FOR PROPOSED RELOCATED (OR NEW) FIXTURES, FBC |
| 1609. |