2014-11-24 12:54:37BUILDING PLAN REVIEW
 PERMIT: 14020179
 PCN: 00-42-43-24-00-000-5251
 P. B. C. TO BE ANNEXED
 ADD: 2132 INDIAN RD
 CONT: CREATIVE CONTRACTING GROUP
 TEL: (561)333-1445
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 NOTICE:!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
 !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
 !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 4TH REVIEW
 DATE: TUES. NOV. 224/ 2014
 ACTION: DENIED
  
 1) ADDRESS/ COMPLIED.
  
 2) 4TH REQUEST. THIS SITE IS BEING ANNEXED INTO THE
 CITY, IT IS LOCATED WITHIN AN A8 FLOOD ZONE. THE
 MINIMUM BASE FLOOD ELEVATION IS 16.00 FT NGVD THE CITY
 OF WEST PALM BEACH REQUIRES AN ADDITIONAL 6 INCHES TO
 THE BASE FLOOD OR A FINISH FLOOR OF 16.5 FT NGVD.
 THE SURVEY INDICATES A FINISH FLOOR OF 16.53 NGVD.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1. BUILDING
 107.3.5.1.1.SITE REQUIREMENTS: FLOOD HAZARD AREAS,
 FLOOD ZONES, AND DESIGN FLOOD ELEVATIONS PROVIDE WHAT
 THE EXISTING FINISH FLOOR ELEVATION IS IN NDVD.
 PLEASE PROVIDE A CURRENT SURVEY SIGNED AND SEALED (2)
 ORIGINALS & FLOOD ZONE CERTIFICATES, THIS STRUCTURE IS
 LOCATED IN A A8 FLOOD ZONE WITH A REQUIRED 16.00 ELE.
 NGVD. THE CITY MUNI CODE FLOOD PREVENTION AND CONTROL
 REQUIRES AN ADDITIONAL 6 INCH FREE BOARD FOR
 RESIDENTIAL AND FOR COMMERCIAL FLOOD PROOFING FOR THE
 SAME 6 INCHES PLUS A ADDITIONAL 6 INCHES IF FLOOD
 PROOFING AND THE FLOOR NOT BEING ABOVE 16.5 FT. NGVD.
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION
  
 NEW COMMENT: PLEASE BE AWARE : THE 2010 FBC-B 1612.4
 DESIGN AND CONSTRUCTION.
 THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES
 LOCATED IN FLOOD HAZARD AREAS, INCLUDING FLOOD HAZARD
 AREAS SUBJECT TO HIGH-VELOCITY WAVE ACTION, SHALL BE IN
 ACCORDANCE WITH CHAPTER 5 OF ASCE 7 AND WITH ASCE
 24.TABLE 7.1 REQUIRES A 1 FT. HEIGHT FOR FINISH FLOOR
 ABOVE THE BASE FLOOD ELEVATION FOR A BUILDING CATEGORY
 II.
  
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANT
 A/C PADS OR OTHER SLABS FOR GENERATORS
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
  
 2) SHEET S-2 SEMI-COMPLIED. THE PREVIOUS REVIEW THE
 PLAN REVIEWER STATED THIS TO BE A S2 OCCUPANCY. FOR
 AUTO REPAIR GAGARES AND BULK TIRE STORAGE WE ARE LOKING
 AT A S-1 OCCUPANCY SEE THE 2010 FBC-B 311.2. THE
 OCCUPANCY LOADING WOULD BE 300 GSF / 12 OCCUPANTS.
  
 3) 4TH REQUEST. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS- MISSING
 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
 1803.6 REPORTING.
 WHERE GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A
 WRITTEN REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED
 TO THE BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED
 AGENT AT THE TIME OF PERMIT APPLICATION
  
 4) 4TH REQUEST. ENGINEERED PLANS FROM DERIK SCHENAVAR
 INDICATE A "C" EXPOSURE BUT THE NEW LUDWIG STEEL
 BUILDING PLANS INDICATE A "B" EXPOSURE.
  
 5) 4TH REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
  
 (31)(C) WALL PANELS.
  
 (31)(D) ROOFING PANELS.
  
 6A) 4TH REQUEST. THE NEW STEEL BUILDING PLANS BY LUDWIG
 WILL NEED TO PROVIDE PRODUCT APPROVALS FOR THE WALL
 PANELS AND ROOFING SYSTEMS. 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6B) 4TH REQUEST. THE LUDWIG STEEL BUILDING PLANS ARE ON
 8 1/2 X 11 SHEETS OF PAPER, THEY DO NOT MEET THE
 REQUIRED SIZE REQUIREMENTS FOR RECORD RETENTION.
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORDS MANAGEMENT.
  
 6C) 4TH REQUEST. WITH THE REDUCED SIZE OF THE ENGINEERS
 SEAL THE PLANS DO NNOT MEET THE SEAL REQUIREMETS.
 61G15-23.001 SEALS ACCEPTABLE TO THE BOARD. SAID SEAL
 SHALL BE A MINIMUM OF 1 7/8 INCHES IN DIAMETER, TO SAY
 LICENSE NOT CERTIFICATE. ALL ENGINEERS MUST BE
 UTILIZING SAID SEAL NO LATER THAN JANUARY 1, 2006.
  
 7) 4TH REQUEST. SHEET S-6 & S-10 BOTH INDICATE THE USE
 OF HELICAL PILES PER COLUMN, IS THERE A SUPPORTING
 SOILS REPORT/ 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED. NO PRODUCT
 INFORMATION FOR THE HELICAL PIERS SHEET S-10 DETAIL # 1
 INDICATES THE USE OF HELICAL PILE WHERE AS DETAIL 2 & 3
 OTH LOOK LIKE AUGER PILE. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 8) 4TH REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) 4TH REQUEST. WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  