Plan Review Notes
Plan Review Notes For Permit 14020179
Permit Number 14020179
Review Stop P
Sequence Number 3
Notes
Date Text
2014-09-22 08:43:059/22/14 - DENIED
 1) SEPARATE SANITARY FACILITIES ARE REQUIRED FOR MALES
 AND FEMALES PER THE 2010 FBC SEC.403.2
 2) BOTH RESTROOMS SHALL BE HANDICAPPED ACCESSIBLE PER
 THE 2010 FBC, ACCESSIBILITY, SEC.213.2.
 3) SHOW THE FIXTURE CLEARANCES IN THE "EMPLOYEE
 RESTROOM". THE FIXTURE SPACEING SHALL COMPLY WITH THE
 2010 FBC ACCESSIBILITY.
 4) SUBMIT A WATER PIPNG DIAGRAM FOR REVIEW. THE WATER
 SUPPLY SYSTEM SHALL COMPLY W/SEC.604 OF THE 2010 FPC
 SEC.WPB AMEND. TO 2010 FBC SEC.107.2.1., 107.3.5.1.
 5) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE EMERGENCY
 EYEWASH/SHOWER AND THE WATERLESS URINAL. THE WATERLESS
 URINAL SHALL COMPLY W/ANSI Z124.9 ( PLASTIC) OR ASME
 A112.19.19 (VITREOUS CHINA). WPB AMEND. TO 2010 FBC
 SEC.107.2.1,
 FPC SEC. 419.1
 6) CLEANOUTS ARE REQD. IN THE BASE OF EACH SOIL OR
 WASTE STACK PER 2010 FBC SEC. 708.3.4.
 7) AS DRAWN, THE SERVICE SINK IS INSTALLED ON A
 HORIZONTAL WET VENT WHICH IS NOT PERMITTED PER THE 2010
 FPC SEC.909.1.
 8) THE URINAL SHALL BE CONNECTED TO A VENTED WASTE
 STACK IF IT IS WALL HUNG. 2010 FPC 901.2.1.
 9) THE VENTS THRU THE ROOF CAN BE 2" IN DIAMETER IN
 LIEU OF 2".
 10) SHT. S-12 - INDICATE THE SLOPE OF THE RAIN GUTTERS
 ON THE PLAN. THE PITCH OF THE GUTTERS AND THE ROOF AREA
 DRAINED SHALL COMPLY WITH TABLE 1106.6 OF THE 2010 FPC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  