Plan Review Notes For Permit 14020179 |
Permit Number |
14020179 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2014-09-22 08:43:05 | 9/22/14 - DENIED | | 1) SEPARATE SANITARY FACILITIES ARE REQUIRED FOR MALES | | AND FEMALES PER THE 2010 FBC SEC.403.2 | | 2) BOTH RESTROOMS SHALL BE HANDICAPPED ACCESSIBLE PER | | THE 2010 FBC, ACCESSIBILITY, SEC.213.2. | | 3) SHOW THE FIXTURE CLEARANCES IN THE "EMPLOYEE | | RESTROOM". THE FIXTURE SPACEING SHALL COMPLY WITH THE | | 2010 FBC ACCESSIBILITY. | | 4) SUBMIT A WATER PIPNG DIAGRAM FOR REVIEW. THE WATER | | SUPPLY SYSTEM SHALL COMPLY W/SEC.604 OF THE 2010 FPC | | SEC.WPB AMEND. TO 2010 FBC SEC.107.2.1., 107.3.5.1. | | 5) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE EMERGENCY | | EYEWASH/SHOWER AND THE WATERLESS URINAL. THE WATERLESS | | URINAL SHALL COMPLY W/ANSI Z124.9 ( PLASTIC) OR ASME | | A112.19.19 (VITREOUS CHINA). WPB AMEND. TO 2010 FBC | | SEC.107.2.1, | | FPC SEC. 419.1 | | 6) CLEANOUTS ARE REQD. IN THE BASE OF EACH SOIL OR | | WASTE STACK PER 2010 FBC SEC. 708.3.4. | | 7) AS DRAWN, THE SERVICE SINK IS INSTALLED ON A | | HORIZONTAL WET VENT WHICH IS NOT PERMITTED PER THE 2010 | | FPC SEC.909.1. | | 8) THE URINAL SHALL BE CONNECTED TO A VENTED WASTE | | STACK IF IT IS WALL HUNG. 2010 FPC 901.2.1. | | 9) THE VENTS THRU THE ROOF CAN BE 2" IN DIAMETER IN | | LIEU OF 2". | | 10) SHT. S-12 - INDICATE THE SLOPE OF THE RAIN GUTTERS | | ON THE PLAN. THE PITCH OF THE GUTTERS AND THE ROOF AREA | | DRAINED SHALL COMPLY WITH TABLE 1106.6 OF THE 2010 FPC. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | |
|