Plan Review Notes
Plan Review Notes For Permit 14020179
Permit Number 14020179
Review Stop B
Sequence Number 3
Notes
Date Text
2014-09-23 12:23:02BUILDING PLAN REVIEW
 PERMIT: 14020179
 PCN: 00-42-43-24-00-000-5251
 P. B. C. TO BE ANNEXED
 ADD: 2132 INDIAN RD
 CONT: CREATIVE CONTRACTING GROUP
 TEL: (561)333-1445
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE:!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
 !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
 !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 3RD REVIEW
 DATE: TUES. SEPT. 23/ 2014
 ACTION: DENIED
  
 1) ADDRESS/ COMPLIED.
  
 2) 3RD REQUEST. THIS SITE IS BEING ANNEXED INTO THE
 CITY, IT IS LOCATED WITHIN AN A8 FLOOD ZONE. THE
 MINIMUM BASE FLOOD ELEVATION IS 16.00 FT NGVD THE CITY
 OF WEST PALM BEACH REQUIRES AN ADDITIONAL 6 INCHES TO
 THE BASE FLOOD OR A FINISH FLOOR OF 16.5 FT NGVD.
 THE SURVEY INDICATES A FINISH FLOOR OF 16.53 NGVD.
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1. BUILDING
 107.3.5.1.1.SITE REQUIREMENTS: FLOOD HAZARD AREAS,
 FLOOD ZONES, AND DESIGN FLOOD ELEVATIONS PROVIDE WHAT
 THE EXISTING FINISH FLOOR ELEVATION IS IN NDVD.
 PLEASE PROVIDE A CURRENT SURVEY SIGNED AND SEALED (2)
 ORIGINALS & FLOOD ZONE CERTIFICATES, THIS STRUCTURE IS
 LOCATED IN A A8 FLOOD ZONE WITH A REQUIRED 16.00 ELE.
 NGVD. THE CITY MUNI CODE FLOOD PREVENTION AND CONTROL
 REQUIRES AN ADDITIONAL 6 INCH FREE BOARD FOR
 RESIDENTIAL AND FOR COMMERCIAL FLOOD PROOFING FOR THE
 SAME 6 INCHES PLUS A ADDITIONAL 6 INCHES IF FLOOD
 PROOFING AND THE FLOOR NOT BEING ABOVE 16.5 FT. NGVD.
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANT
 A/C PADS OR OTHER SLABS FOR GENERATORS
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
  
 2) SHEET S-2 SEMI-COMPLIED. THE PREVIOUS REVIEW THE
 PLAN REVIEWER STATED THIS TO BE A S2 OCCUPANCY. FOR
 AUTO REPAIR GAGARES AND BULK TIRE STORAGE WE ARE LOKING
 AT A S-1 OCCUPANCY SEE THE 2010 FBC-B 311.2. THE
 OCCUPANCY LOADING WOULD BE 300 GSF / 12 OCCUPANTS.
  
 3) 3RD REQUEST. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS- MISSING
 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
 1803.6 REPORTING.
 WHERE GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A
 WRITTEN REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED
 TO THE BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED
 AGENT AT THE TIME OF PERMIT APPLICATION
  
 4) SEMI -COMPLIED. ENGINEERED PLANS FROM DERIK
 SCHENAVAR INDICATE A "C" EXPOSURE BUT THE NEW LUDWIG
 STEEL BUILDING PLANS INDICATE A "B" EXPOSURE.
  
 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
  
 (31)(C) WALL PANELS.
  
 (31)(D) ROOFING PANELS.
  
 6A) THE NEW STEEL BUILDING PLANS BY LUDWIG WILL NEED TO
 PROVIDE PRODUCT APPROVALS FOR THE WALL PANELS AND
 ROOFING SYSTEMS. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6B) THE LUDWIG STEEL BUILDING PLANS ARE ON 8 1/2 X 11
 SHEETS OF PAPER, THEY DO NOT MEET THE REQUIRED SIZE
 REQUIREMENTS FOR RECORD RETENTION.
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORDS MANAGEMENT.
  
 6C) WITH THE REDUCED SIZE OF THE ENGINEERS SEAL THE
 PLANS DO NNOT MEET THE SEAL REQUIREMETS. 61G15-23.001
 SEALS ACCEPTABLE TO THE BOARD. SAID SEAL SHALL BE A
 MINIMUM OF 1 7/8 INCHES IN DIAMETER, TO SAY LICENSE NOT
 CERTIFICATE. ALL ENGINEERS MUST BE UTILIZING SAID SEAL
 NO LATER THAN JANUARY 1, 2006.
  
 7) SHEET S-6 & S-10 BOTH INDICATE THE USE OF HELICAL
 PILES PER COLUMN, IS THERE A SUPPORTING SOILS REPORT/
 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED. NO PRODUCT
 INFORMATION FOR THE HELICAL PIERS SHEET S-10 DETAIL # 1
 INDICATES THE USE OF HELICAL PILE WHERE AS DETAIL 2 & 3
 OTH LOOK LIKE AUGER PILE. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  