Date |
Text |
2014-09-23 12:23:02 | BUILDING PLAN REVIEW |
| PERMIT: 14020179 |
| PCN: 00-42-43-24-00-000-5251 |
| P. B. C. TO BE ANNEXED |
| ADD: 2132 INDIAN RD |
| CONT: CREATIVE CONTRACTING GROUP |
| TEL: (561)333-1445 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| NOTICE:!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!! |
| !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!! |
| !!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!! |
| CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| FEE FOR |
| PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES |
| FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| |
| 3RD REVIEW |
| DATE: TUES. SEPT. 23/ 2014 |
| ACTION: DENIED |
| |
| 1) ADDRESS/ COMPLIED. |
| |
| 2) 3RD REQUEST. THIS SITE IS BEING ANNEXED INTO THE |
| CITY, IT IS LOCATED WITHIN AN A8 FLOOD ZONE. THE |
| MINIMUM BASE FLOOD ELEVATION IS 16.00 FT NGVD THE CITY |
| OF WEST PALM BEACH REQUIRES AN ADDITIONAL 6 INCHES TO |
| THE BASE FLOOD OR A FINISH FLOOR OF 16.5 FT NGVD. |
| THE SURVEY INDICATES A FINISH FLOOR OF 16.53 NGVD. |
| |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1. BUILDING |
| 107.3.5.1.1.SITE REQUIREMENTS: FLOOD HAZARD AREAS, |
| FLOOD ZONES, AND DESIGN FLOOD ELEVATIONS PROVIDE WHAT |
| THE EXISTING FINISH FLOOR ELEVATION IS IN NDVD. |
| PLEASE PROVIDE A CURRENT SURVEY SIGNED AND SEALED (2) |
| ORIGINALS & FLOOD ZONE CERTIFICATES, THIS STRUCTURE IS |
| LOCATED IN A A8 FLOOD ZONE WITH A REQUIRED 16.00 ELE. |
| NGVD. THE CITY MUNI CODE FLOOD PREVENTION AND CONTROL |
| REQUIRES AN ADDITIONAL 6 INCH FREE BOARD FOR |
| RESIDENTIAL AND FOR COMMERCIAL FLOOD PROOFING FOR THE |
| SAME 6 INCHES PLUS A ADDITIONAL 6 INCHES IF FLOOD |
| PROOFING AND THE FLOOR NOT BEING ABOVE 16.5 FT. NGVD. |
| FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES |
| SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. |
| (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| ELEVATION CERTIFICATE IS REQUIRED |
| (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANT |
| A/C PADS OR OTHER SLABS FOR GENERATORS |
| |
| FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| JULY 31,2015 |
| |
| FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| |
| 2) SHEET S-2 SEMI-COMPLIED. THE PREVIOUS REVIEW THE |
| PLAN REVIEWER STATED THIS TO BE A S2 OCCUPANCY. FOR |
| AUTO REPAIR GAGARES AND BULK TIRE STORAGE WE ARE LOKING |
| AT A S-1 OCCUPANCY SEE THE 2010 FBC-B 311.2. THE |
| OCCUPANCY LOADING WOULD BE 300 GSF / 12 OCCUPANTS. |
| |
| 3) 3RD REQUEST. STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| SOIL CONDITIONS/ANALYSIS- MISSING |
| 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| 1803.6 REPORTING. |
| WHERE GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A |
| WRITTEN REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED |
| TO THE BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED |
| AGENT AT THE TIME OF PERMIT APPLICATION |
| |
| 4) SEMI -COMPLIED. ENGINEERED PLANS FROM DERIK |
| SCHENAVAR INDICATE A "C" EXPOSURE BUT THE NEW LUDWIG |
| STEEL BUILDING PLANS INDICATE A "B" EXPOSURE. |
| |
| 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| |
| (31)(C) WALL PANELS. |
| |
| (31)(D) ROOFING PANELS. |
| |
| 6A) THE NEW STEEL BUILDING PLANS BY LUDWIG WILL NEED TO |
| PROVIDE PRODUCT APPROVALS FOR THE WALL PANELS AND |
| ROOFING SYSTEMS. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 6B) THE LUDWIG STEEL BUILDING PLANS ARE ON 8 1/2 X 11 |
| SHEETS OF PAPER, THEY DO NOT MEET THE REQUIRED SIZE |
| REQUIREMENTS FOR RECORD RETENTION. |
| 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN |
| ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION |
| PROGRAM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM |
| SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED |
| TO RECORDS MANAGEMENT. |
| |
| 6C) WITH THE REDUCED SIZE OF THE ENGINEERS SEAL THE |
| PLANS DO NNOT MEET THE SEAL REQUIREMETS. 61G15-23.001 |
| SEALS ACCEPTABLE TO THE BOARD. SAID SEAL SHALL BE A |
| MINIMUM OF 1 7/8 INCHES IN DIAMETER, TO SAY LICENSE NOT |
| CERTIFICATE. ALL ENGINEERS MUST BE UTILIZING SAID SEAL |
| NO LATER THAN JANUARY 1, 2006. |
| |
| 7) SHEET S-6 & S-10 BOTH INDICATE THE USE OF HELICAL |
| PILES PER COLUMN, IS THERE A SUPPORTING SOILS REPORT/ |
| 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. NO PRODUCT |
| INFORMATION FOR THE HELICAL PIERS SHEET S-10 DETAIL # 1 |
| INDICATES THE USE OF HELICAL PILE WHERE AS DETAIL 2 & 3 |
| OTH LOOK LIKE AUGER PILE. 107.2.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |