2014-05-02 12:27:26 | PLUMBING PLAN REVIEW |
| PERMIT: 14020179 |
| PCN: 00-42-43-24-00-000-5251 |
| P. B. C. TO BE ANNEXED |
| ADD: 2321 INDIAN RD VS. 2131 INDIAN RD |
| CONT: CREATIVE CONTRACTING GROUP |
| TEL: (561)333-1445 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE:FRIDAY APRIL 02/ 2014 |
| ACTION: DENIED |
| |
| 1-2) COMPLIED. SHEET S7 INDICATES THE OCCUPANCY AS A F1 |
| LIGHT AUTO REPAIR/ USED TIRE SALE, PLEASE REVIEW 2010 |
| FBC-B 406.6 REPAIR GARAGES ARE SPECIAL OCCUPANCIES |
| LISTED AS A S2. |
| |
| 3) 2ND REQUEST. THE SANITARY PLANS ARE DRAWN USING A |
| WET VENT SYSTEM. WATER CLOSETS, AND SERVICE SINKS DO |
| NOT HAVE VENTS. SEE 2010 FBC-PLUMBING |
| 907.1 INDIVIDUAL VENT PERMITTED. |
| EACH TRAP AND TRAPPED FIXTURE IS PERMITTED TO BE |
| PROVIDED WITH AN INDIVIDUAL VENT. THE INDIVIDUAL VENT |
| SHALL CONNECT TO THE FIXTURE DRAIN OF THE TRAP OR |
| TRAPPED FIXTURE BEING VENTED. |
| 908.1 INDIVIDUAL VENT AS COMMON VENT. |
| AN INDIVIDUAL VENT IS PERMITTED TO VENT TWO TRAPS OR |
| TRAPPED FIXTURES AS A COMMON VENT. THE TRAPS OR TRAPPED |
| FIXTURES BEING COMMON VENTED SHALL BE LOCATED ON THE |
| SAME FLOOR LEVEL. |
| |
| 908.2 CONNECTION AT THE SAME LEVEL. |
| WHERE THE FIXTURE DRAINS BEING COMMON VENTED CONNECT AT |
| THE SAME LEVEL, THE VENT CONNECTION SHALL BE AT THE |
| INTERCONNECTION OF THE FIXTURE DRAINS OR DOWNSTREAM OF |
| THE INTERCONNECTION. |
| |
| 908.3 CONNECTION AT DIFFERENT LEVELS. |
| WHERE THE FIXTURE DRAINS CONNECT AT DIFFERENT LEVELS, |
| THE VENT SHALL CONNECT AS A VERTICAL EXTENSION OF THE |
| VERTICAL DRAIN. THE VERTICAL DRAIN PIPE CONNECTING THE |
| TWO FIXTURE DRAINS SHALL BE CONSIDERED THE VENT FOR THE |
| LOWER FIXTURE DRAIN, AND SHALL BE SIZED IN ACCORDANCE |
| WITH TABLE 908.3. THE UPPER FIXTURE SHALL NOT BE A |
| WATER CLOSET. |
| FLORIDA BUILDING CODE INFORMAL INTERPRETATION: |
| DATE: WED DEC 17 2003 |
| REPORT #: 2241 |
| CODE: PLUMBING |
| SECTION: 909.1 |
| QUESTION: |
| IS IT THE INTENT OF SECTION 909.1 WET VENTING TO |
| EXCLUDE URINALS AS A FIXTURE TO BE ALLOW AS PART OF A |
| WET |
| VENTED SYSTEM? |
| ANSWER: |
| NO. WET VENTING RELIES ON LOW FLOW VELOCITY, LOW FLOW |
| RATES, AND LOW PROBABILITY OF SIMULTANEOUS |
| DISCHARGE. FOR THAT REASON, WET VENTING IS LIMITED TO |
| TWO BATHROOM GROUPS, LOCATED ON THE SAME FLOOR LEVEL. |
| ALTHOUGH A BATHROOM GROUP BY DEFINITION DOES NOT |
| INCLUDE URINALS, URINALS MAY BE REGARDED AS SIMILAR IN |
| FUNCTION TO WATER CLOSETS (SEE 419.2), AND THEY PLACE |
| LESS RELATIVE LOAD ON THE DRAINAGE SYSTEM. URINALS, AS |
| WELL AS EMERGENCY FLOOR DRAINS AND DRINKING FOUNTAINS, |
| MAY BE INCLUDED IN A WET VENT SYSTEM, WITHIN THE |
| LIMITS OF TABLE 909.3. PLEASE NOTE! 12/17/2003-UPON |
| CHALLENGE AND FURTHER REVIEW |
| THIS INTERPRETATION IS MODIFIED AS FOLLOWS: 1) THE CODE |
| PERMITS WET VENTING OF BATHROOM |
| GROUPS, 2) THE DEFINITION OF A BATHROOM GROUP DOES NOT |
| SPECIFICALLY INCLUDE A URINAL, THEREFORE 3) A URINAL |
| MAY NOT BE A PART OF A WET VENT SYSTEM. |
| COMMENTARY: |
| KITCHEN SINKS, WASHING MACHINES AND SIMILAR HIGHER |
| VOLUME FIXTURES WOULD NOT BE PERMITTED ON A WET VENT |
| SYSTEM, AND WOULD HAVE TO DISCHARGE DOWNSTREAM OF THE |
| WET VENT. 12/17/2003-COMMENTARY |
| MODIFICATION: PROPERLY SIZED WET VENTING RESULTS IN |
| ADEQUATE AIRFLOW IN THE WET-VENTED PIPE TO |
| PREVENT THE FIXTURES FROM BEING SUBJECT TO SIPHONAGE OR |
| BACKPRESSURE (PLUS OR MINUS 1-INCH OF WATER |
| COLUMN). THE ORIGINAL INTERPRETATION MET THE INTENT, IF |
| NOT THE LETTER, OF THE CODE SINCE URINALS HAVE, FOR A |
| NUMBER OF YEARS NOW, BEEN LIMITED TO 1 GALLON PER |
| FLUSHING CYCLE. AS LONG AS THE WET VENT IS LIMITED TO |
| TWO |
| BATHROOM GROUPS, THERE IS PROBABLY NO FIELD |
| CONFIGURATION CONTAINING A URINAL THAT WOULD POSE A |
| PROBLEM |
| BUT STRICT APPLICATION OF THE CODE WILL NOT ALLOW IT. |
| |
| 4) COMPLIED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |