2014-03-04 15:46:55AS PER FBC-B 406.6 REPAIR GARAGES, THIS TYPE OF
 ESTABLISHMENT REQUIRES MECHANICAL VENTILATION WHICH IS
 CONTROLLED AT THE ENTRANCE TO THE GARAGE. THE SUBMITTED
 DRAWINGS DO NOT INCLUDE EITHER OF THE COMPONENTS
 REQUIRED, THE EXHAUST FAN OR THE CONTROLLER.