2014-02-25 11:50:08 | BUILDING PLAN REVIEW |
| PERMIT: 14020179 |
| PCN: 00-42-43-24-00-000-5251 |
| P. B. C. TO BE ANNEXED |
| ADD: 2321 INDIAN RD VS. 2131 INDIAN RD |
| CONT: CREATIVE CONTRACTING GROUP |
| TEL: (561)333-1445 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. FEB. 25/ 2014 |
| ACTION: DENIED |
| |
| 1) PLEASE REVIEW THE ABOVE PROPERTY CONTROL NUMBER TO |
| VERIFY THIS IS THE PROPERTY THAT IS GOING TO BE ANNEXED |
| INTO THE CITY OF W.P.B. |
| NOTE THERE ARE TWO ADDRESSES LISTED IN THE ADDRESS |
| FIELD ABOVE. THE P.B.C. PROPERTY APPRAISERS SITE HAS |
| THE ADDRESS OF 2132 INDIAN RD. THE PERMIT APPLICATION |
| HAS THE ADDRESS AS 2312 INDIAN RD. PLEASE VERIFY THE |
| PROPERTY APPRAISERS SITE IS CORRECT AND CORRECT THE |
| ADDRESS ON THE PERMIT APPLICATION. WHEN THIS PROPERTY |
| IS TRANSFEERED, RECORDED THE ADDRESS NEEDS TO BE |
| CORRECT, WITH ALL RECORDS BEING SUBMITTED FOR |
| PERMITING. |
| |
| 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| 2.1.SITE REQUIREMENTS: FLOOD HAZARD AREAS, FLOOD ZONES, |
| AND DESIGN FLOOD ELEVATIONS PROVIDE WHAT THE EXISTING |
| FINISH FLOOR ELEVATION IS IN NDVD |
| |
| 2.2 SHEET S7 INDICATES THE OCCUPANCY AS A F1 LIGHT AUTO |
| REPAIR/ USED TIRE SALE, PLEASE REVIEW 2010 FBC-B 406.6 |
| REPAIR GARAGES ARE SPECIAL OCCUPANCIES LISTED AS A S2. |
| |
| 2.3) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| SPECIFIC OCCUPANCY REQUIREMENTS |
| |
| 2.4 STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| SOIL CONDITIONS/ANALYSIS |
| BUILDING ENVELOPE: PRODUCT APPROVALS |
| FOUNDATION |
| FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612, |
| INCLUDING LOWEST FLOOR ELEVATIONS, ENCLOSURES, FLOOD |
| DAMAGE-RESISTANT MATERIALS |
| |
| |
| 3) PLEASE PROVIDE A CURRENT SURVEY SIGNED AND SEALED |
| (2) ORIGINALS & FLOOD ZONE CERTIFICATES, THIS STRUCTURE |
| IS LOCATED IN A A8 FLOOD ZONE WITH A REQUIRED 16.00 |
| ELE. NGVD. THE CITY MUNI CODE FLOOD PREVENTION AND |
| CONTROL REQUIRES AN ADDITIONAL 6 INCH FREE BOARD FOR |
| RESIDENTIAL AND FOR COMMERCIAL FLOOD PROOFING FOR THE |
| SAME 6 INCHES PLUS A ADDITIONAL 6 INCHES IF FLOOD |
| PROOFING AND THE FLOOR NOT BEING ABOVE 16.5 FT. NGVD. |
| FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES |
| SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION |
| |
| DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE |
| REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| REQUIRED: |
| (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| HEIGHT. |
| (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| ELEVATION CERTIFICATE IS REQUIRED |
| (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| ATTENDANT |
| A/C PADS OR OTHER SLABS FOR GENERATORS |
| |
| FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| JULY 31,2015 |
| |
| FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| |
| 4) SHEET S-6 INDICATES THE WIND DESIGN TO A EXPOSURE D/ |
| 170 MPH, 3 SECOND GUST. THE DESIGNER OF RECORD CAN |
| DESIGN TO THIS MORE STRINGENT DESIGN, THE BUILDING IS |
| LOCATED IN A WIND EXPOSURE C/ 170 MPH WIND ZONE. PLEASE |
| PROVIDE PRESSURES FOR COMPONENTS AND CLADDING FOR WALL |
| ZONES AND ROOF ZONES. PLEASE NOTE THAT WE DO USE 10 SQ |
| FT FOR COMPONENTS AND CLADDING FOR ROOFING MATERIALS. |
| 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| CHAPTER 6 OF ASCE 7-10. |
| 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| |
| 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (D) ROOFING PRODUCTS AND ASSEMBLIES FOR FLAT ROOFS |
| PLEASE IDENTIFY SUB-SYSTEMS AND ASSOCIATED PRESSURES, |
| REVIEW LIMITATIONS FOR THIS APPROVAL. |
| |
| 7) SHEET S-6 & S-10 BOTH INDICATE THE USE OF HELICAL |
| PILES PER COLUMN, IS THERE A SUPPORTING SOILS REPORT/ |
| 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| |
| 8) SHEET S-10 DETAIL # 1 INDICATES THE USE OF HELICAL |
| PILE WHERE AS DETAIL 2 & 3 OTH LOOK LIKE AUGER PILE? |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 9) S12 THERE IS A NOTE TO HAVE THE ROLL ROOFING TO GO |
| OVER THE TOP OF THE WALL AND DOWNWARD ON THE WALL FOR |
| 16 INCHES? PLEASE EXPLAIN WHY THE ROOFING CONTINUES |
| DOWN THE WALL FOR 16 INCHES? ALSO SHOW COMPLIANCE WITH |
| 2010 FBC-B: 1503.4.3 GUTTERS. |
| GUTTERS AND LEADERS PLACED ON THE OUTSIDE OF BUILDINGS, |
| OTHER THAN GROUP R-3, PRIVATE GARAGES AND BUILDINGS OF |
| TYPE V CONSTRUCTION, SHALL BE OF NONCOMBUSTIBLE |
| MATERIAL OR A MINIMUM OF SCHEDULE 40 PLASTIC PIPE. |
| |
| 1503.7 PROTECTION AGAINST DECAY AND TERMITES. |
| CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR |
| SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| A ROOF ABOVE ANOTHER ROOF. |
| |
| SIZE TO THE GUTTER AND ROOF LEADERS TO BE SIZED TO THE |
| REQUIREMENTS FOUND IN THE 2010 FBC-P. |
| |
| 10) 406.6.1 GENERAL. |
| REPAIR GARAGES SHALL BE CONSTRUCTED IN ACCORDANCE WITH |
| THE FLORIDA FIRE PREVENTION CODE AND SECTIONS 406.6.1 |
| THROUGH 406.6.6. THIS OCCUPANCY SHALL NOT INCLUDE MOTOR |
| FUEL-DISPENSING FACILITIES, AS REGULATED IN SECTION |
| 406.5. |
| |
| 11) |
| |
| 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |