Plan Review Notes
Plan Review Notes For Permit 14020179
Permit Number 14020179
Review Stop B
Sequence Number 1
Notes
Date Text
2014-02-25 11:50:08BUILDING PLAN REVIEW
 PERMIT: 14020179
 PCN: 00-42-43-24-00-000-5251
 P. B. C. TO BE ANNEXED
 ADD: 2321 INDIAN RD VS. 2131 INDIAN RD
 CONT: CREATIVE CONTRACTING GROUP
 TEL: (561)333-1445
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 25/ 2014
 ACTION: DENIED
  
 1) PLEASE REVIEW THE ABOVE PROPERTY CONTROL NUMBER TO
 VERIFY THIS IS THE PROPERTY THAT IS GOING TO BE ANNEXED
 INTO THE CITY OF W.P.B.
 NOTE THERE ARE TWO ADDRESSES LISTED IN THE ADDRESS
 FIELD ABOVE. THE P.B.C. PROPERTY APPRAISERS SITE HAS
 THE ADDRESS OF 2132 INDIAN RD. THE PERMIT APPLICATION
 HAS THE ADDRESS AS 2312 INDIAN RD. PLEASE VERIFY THE
 PROPERTY APPRAISERS SITE IS CORRECT AND CORRECT THE
 ADDRESS ON THE PERMIT APPLICATION. WHEN THIS PROPERTY
 IS TRANSFEERED, RECORDED THE ADDRESS NEEDS TO BE
 CORRECT, WITH ALL RECORDS BEING SUBMITTED FOR
 PERMITING.
  
 2) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 2.1.SITE REQUIREMENTS: FLOOD HAZARD AREAS, FLOOD ZONES,
 AND DESIGN FLOOD ELEVATIONS PROVIDE WHAT THE EXISTING
 FINISH FLOOR ELEVATION IS IN NDVD
  
 2.2 SHEET S7 INDICATES THE OCCUPANCY AS A F1 LIGHT AUTO
 REPAIR/ USED TIRE SALE, PLEASE REVIEW 2010 FBC-B 406.6
 REPAIR GARAGES ARE SPECIAL OCCUPANCIES LISTED AS A S2.
  
 2.3) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 SPECIFIC OCCUPANCY REQUIREMENTS
  
 2.4 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 SOIL CONDITIONS/ANALYSIS
 BUILDING ENVELOPE: PRODUCT APPROVALS
 FOUNDATION
 FLOOD REQUIREMENTS IN ACCORDANCE WITH SECTION 1612,
 INCLUDING LOWEST FLOOR ELEVATIONS, ENCLOSURES, FLOOD
 DAMAGE-RESISTANT MATERIALS
  
  
 3) PLEASE PROVIDE A CURRENT SURVEY SIGNED AND SEALED
 (2) ORIGINALS & FLOOD ZONE CERTIFICATES, THIS STRUCTURE
 IS LOCATED IN A A8 FLOOD ZONE WITH A REQUIRED 16.00
 ELE. NGVD. THE CITY MUNI CODE FLOOD PREVENTION AND
 CONTROL REQUIRES AN ADDITIONAL 6 INCH FREE BOARD FOR
 RESIDENTIAL AND FOR COMMERCIAL FLOOD PROOFING FOR THE
 SAME 6 INCHES PLUS A ADDITIONAL 6 INCHES IF FLOOD
 PROOFING AND THE FLOOR NOT BEING ABOVE 16.5 FT. NGVD.
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
 PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS
 REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE
 PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR
 HEIGHT.
 (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED
 (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANT
 A/C PADS OR OTHER SLABS FOR GENERATORS
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 JULY 31,2015
  
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015.
  
 4) SHEET S-6 INDICATES THE WIND DESIGN TO A EXPOSURE D/
 170 MPH, 3 SECOND GUST. THE DESIGNER OF RECORD CAN
 DESIGN TO THIS MORE STRINGENT DESIGN, THE BUILDING IS
 LOCATED IN A WIND EXPOSURE C/ 170 MPH WIND ZONE. PLEASE
 PROVIDE PRESSURES FOR COMPONENTS AND CLADDING FOR WALL
 ZONES AND ROOF ZONES. PLEASE NOTE THAT WE DO USE 10 SQ
 FT FOR COMPONENTS AND CLADDING FOR ROOFING MATERIALS.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (D) ROOFING PRODUCTS AND ASSEMBLIES FOR FLAT ROOFS
 PLEASE IDENTIFY SUB-SYSTEMS AND ASSOCIATED PRESSURES,
 REVIEW LIMITATIONS FOR THIS APPROVAL.
  
 7) SHEET S-6 & S-10 BOTH INDICATE THE USE OF HELICAL
 PILES PER COLUMN, IS THERE A SUPPORTING SOILS REPORT/
 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 8) SHEET S-10 DETAIL # 1 INDICATES THE USE OF HELICAL
 PILE WHERE AS DETAIL 2 & 3 OTH LOOK LIKE AUGER PILE?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 9) S12 THERE IS A NOTE TO HAVE THE ROLL ROOFING TO GO
 OVER THE TOP OF THE WALL AND DOWNWARD ON THE WALL FOR
 16 INCHES? PLEASE EXPLAIN WHY THE ROOFING CONTINUES
 DOWN THE WALL FOR 16 INCHES? ALSO SHOW COMPLIANCE WITH
 2010 FBC-B: 1503.4.3 GUTTERS.
 GUTTERS AND LEADERS PLACED ON THE OUTSIDE OF BUILDINGS,
 OTHER THAN GROUP R-3, PRIVATE GARAGES AND BUILDINGS OF
 TYPE V CONSTRUCTION, SHALL BE OF NONCOMBUSTIBLE
 MATERIAL OR A MINIMUM OF SCHEDULE 40 PLASTIC PIPE.
  
 1503.7 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 SIZE TO THE GUTTER AND ROOF LEADERS TO BE SIZED TO THE
 REQUIREMENTS FOUND IN THE 2010 FBC-P.
  
 10) 406.6.1 GENERAL.
 REPAIR GARAGES SHALL BE CONSTRUCTED IN ACCORDANCE WITH
 THE FLORIDA FIRE PREVENTION CODE AND SECTIONS 406.6.1
 THROUGH 406.6.6. THIS OCCUPANCY SHALL NOT INCLUDE MOTOR
 FUEL-DISPENSING FACILITIES, AS REGULATED IN SECTION
 406.5.
  
 11)
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  