Plan Review Notes For Permit 14020114 |
Permit Number |
14020114 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-02-18 14:02:57 | 455 HIBISCUS | | PERMIT #14020114 | | MASTER #13070994 (DIGITAL) | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO - SUBMIT REVISION***** | | | | GENERAL: PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT | | CONNECTIONS. | | | | SHEET FP-2: COULD NOT LOCATE ANY FIRE PROTECTION IN | | STAIR #144. | | | | SHEET FP-8: ELIMINATE THE 1-1/2" REDUCER ON THE HOSE | | VALVES. | | | | SHEET FP-8: PROVIDE A SEPARATE DETAIL FOR THE PRESSURE | | REGULATING DEVICES. NOTE PER NFPA 13 A PRESSURE GAUGE | | IS NEEDED ON THE INLET AND OUTLET SIDES OF THE PRESSURE | | REDUCING VALVE AND A LISTED INDICATING VALVE IS NEEDED | | ON THE INLET SIDE OF EACH PRESSURE REDUCING VALVE | | UNLESS THE VALVE MEETS THE LISTING REQUIREMENTS FOR USE | | AS AN INDICATING VALVE. | | | | EQUIPMENT CUT SHEETS: SUBMIT PRODUCT DATA FOR PRESSURE | | REGULATING DEVICES. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|