Plan Review Notes
Plan Review Notes For Permit 14020114
Permit Number 14020114
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-02-18 14:02:57455 HIBISCUS
 PERMIT #14020114
 MASTER #13070994 (DIGITAL)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 GENERAL: PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTIONS.
  
 SHEET FP-2: COULD NOT LOCATE ANY FIRE PROTECTION IN
 STAIR #144.
  
 SHEET FP-8: ELIMINATE THE 1-1/2" REDUCER ON THE HOSE
 VALVES.
  
 SHEET FP-8: PROVIDE A SEPARATE DETAIL FOR THE PRESSURE
 REGULATING DEVICES. NOTE PER NFPA 13 A PRESSURE GAUGE
 IS NEEDED ON THE INLET AND OUTLET SIDES OF THE PRESSURE
 REDUCING VALVE AND A LISTED INDICATING VALVE IS NEEDED
 ON THE INLET SIDE OF EACH PRESSURE REDUCING VALVE
 UNLESS THE VALVE MEETS THE LISTING REQUIREMENTS FOR USE
 AS AN INDICATING VALVE.
  
 EQUIPMENT CUT SHEETS: SUBMIT PRODUCT DATA FOR PRESSURE
 REGULATING DEVICES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  