2014-02-06 11:22:14 | 2010 FBC | | | | DENIED | | | | 1) BASED ON THE DRAWING THAT WAS SUBMITTED, IT APPEARS | | THAT ONE OF THE UPSTAIRS BEDROOMS DOES NOT HAVE AN | | EMERGENCY ESCAPE AND RESCUE OPENING THAT COMPLIES WITH | | FBCR310.1. PLEASE CLARIFY IF THERE IS ONE FOR THIS | | BEDROOM OR SHOW COMPLIANCE WITH THE EXCEPTION TO FBC | | EXISTING BUILDING SECTION 604.1 WHICH ALLOWS NO MORE | | THAN A 5 PERCENT REDUCTION IN THE CLEAR OPENING | | DIMENSIONS OF REPLACEMENT DOORS AND WINDOWS. | | | | 2) THE COMPONENT AND CLADDING WIND PRESSURE CHART THAT | | WAS SUBMITTED IS NOT CORRECT. THE WINDOW DIAGRAM | | DRAWING SPECIFIES THE MEAN ROOF HEIGHT AS 23 FEET AND | | THE C & C CHART HAS 20 FEET. ALL OF THE WINDOWS ARE | | INDICATED AS BEING IN WALL ZONE 5 (WITHIN 4' OF AN | | EXTERIOR CORNER). THE PRESSURES FOR A 10 SQFT WALL AREA | | IN A BUILDING LOCATED IN THE 170 MPH WIND SPEED, | | EXPOSURE C WITH A 20 ' MRH ARE POSITIVE 40.4 AND | | NEGATIVE 54.1. PLEASE CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|