Notes
Date Text
2014-02-06 11:22:142010 FBC
  
 DENIED
  
 1) BASED ON THE DRAWING THAT WAS SUBMITTED, IT APPEARS
 THAT ONE OF THE UPSTAIRS BEDROOMS DOES NOT HAVE AN
 EMERGENCY ESCAPE AND RESCUE OPENING THAT COMPLIES WITH
 FBCR310.1. PLEASE CLARIFY IF THERE IS ONE FOR THIS
 BEDROOM OR SHOW COMPLIANCE WITH THE EXCEPTION TO FBC
 EXISTING BUILDING SECTION 604.1 WHICH ALLOWS NO MORE
 THAN A 5 PERCENT REDUCTION IN THE CLEAR OPENING
 DIMENSIONS OF REPLACEMENT DOORS AND WINDOWS.
  
 2) THE COMPONENT AND CLADDING WIND PRESSURE CHART THAT
 WAS SUBMITTED IS NOT CORRECT. THE WINDOW DIAGRAM
 DRAWING SPECIFIES THE MEAN ROOF HEIGHT AS 23 FEET AND
 THE C & C CHART HAS 20 FEET. ALL OF THE WINDOWS ARE
 INDICATED AS BEING IN WALL ZONE 5 (WITHIN 4' OF AN
 EXTERIOR CORNER). THE PRESSURES FOR A 10 SQFT WALL AREA
 IN A BUILDING LOCATED IN THE 170 MPH WIND SPEED,
 EXPOSURE C WITH A 20 ' MRH ARE POSITIVE 40.4 AND
 NEGATIVE 54.1. PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW