Plan Review Notes For Permit 14020098
Permit Number 14020098
Review Stop E
Sequence Number 1
Notes
Date Text
2014-02-25 10:44:2914020098
 5713 CORPORATE WAY
 ADDITION OF TWO DUCT DETECTORS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE SPECIFICATIONS ON THE DUCT DETECTORS. NEC 110.3
 PROVIDE BATTERY CALCULATION FOR THE ALARM SYSTEM. NFPA
 72, 4.5.1
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
  
  