Plan Review Notes
Plan Review Notes For Permit 14011775
Permit Number 14011775
Review Stop M
Sequence Number 2
Notes
Date Text
2014-08-18 14:17:102010 FBC
  
 MECHANICAL REVIEW IS DENIED
  
 NOTE: NO MECHANICAL PLANS WERE SUBMITTED WITH THE
 MASTER. THE BUILDING CONTRACTOR REQUESTED THE
 MECHANICAL TO BE A SEPARATE PERMIT.
  
 1) SUBMIT TWO SETS OF MECHANICAL PLANS WITH DUCT SIZES,
 LOCATIONS, GRILL SIZES, CFMS. SPECIFY THE LOCATIONS OF
 THE MECHANICAL EQUIPMENT ON THE PLANS. CITY AMENDMENTS
 107.3.5.3 ( THE SUPPLY AND RETURN GRILL SIZES WERE NOT
 SPECIFIED ON THE PLANS. )
  
 2) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS.
 FBCR M1401.3 ( THE CALCULATIONS THAT WERE SUBMITTED ARE
 NOT ACCEPTABLE IN THIS JURISDICTION. THE CALCS. DO NOT
 MATCH THE THE EQUIPMENT. 27,637 BTU VS. 40,000 BTU )
  
 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL
 PLANS THAT MATCHES THE EQUIPMENT SIZING CALCULATIONS.
 CITY AMENDMENTS 107.3.5.3 ( THERE IS NO EQUIPMENT
 SCHEDULE ON THE PLANS. )
  
 4) COMPLIED.
  
 5) SPECIFY THE VALUE OF THE MECHANICAL WORK FOR THIS
 PROJECT. CITY AMENDMENTS 109.3 ( THIS ITEM WAS NOT
 ADDRESSED. )
  
 6) NEW COMMENT. THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN IS REQUIRED ON THE PLANS.
 CITY AMENDMENTS 107.2.1
  
 7) NEW COMMENT. IN THE BOTTOM RIGHT OF THE PLAN, IT IS
 SPECIFIED THAT THIS IS AN A/C CHANGE OUT. IN ORDER TO
 AVOID CONFUSION, PLEASE CHANGE TO INDICATE THAT THIS IS
 A NEW INSTALLATION. CITY AMENDMENTS 107.2.1
  