Plan Review Notes For Permit 14011775 |
Permit Number |
14011775 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-02-10 09:14:41 | 2010 FBC | | | | MECHANICAL REVIEW IS DENIED | | | | NOTE: NO MECHANICAL PLANS WERE SUBMITTED WITH THE | | MASTER. THE BUILDING CONTRACTOR REQUESTED THE | | MECHANICAL TO BE A SEPARATE PERMIT. | | | | 1) SUBMIT TWO SETS OF MECHANICAL PLANS WITH DUCT SIZES, | | LOCATIONS, GRILL SIZES, CFMS. SPECIFY THE LOCATIONS OF | | THE MECHANICAL EQUIPMENT ON THE PLANS. CITY AMENDMENTS | | 107.3.5.3 | | | | 2) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS. | | FBCR M1401.3 | | | | 3) PROVIDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL | | PLANS THAT MATCHES THE EQUIPMENT SIZING CALCULATIONS. | | CITY AMENDMENTS 107.3.5.3 | | | | 4) SHOW COMPLIANCE WITH FBCR M1602.4 FOR BALANCED | | RETURN AIR. | | | | 5) SPECIFY THE VALUE OF THE MECHANICAL WORK FOR THIS | | PROJECT. CITY AMENDMENTS 109.3 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|