2014-02-05 07:27:46PLUMBING PLAN REVIEW
 PERMIT: 14011728
 ADD: 2751 S DIXIE HWY
 CONT: NORTH COUNTY PLUMBING
 TEL: (561)625-9414
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED. FEB. 05/ 2014
 ACTION: DENIED
  
 SCOPE OF WORK: REPIPE COMMERCIAL DISPOSAL INTO GREASE
 SYSTEM, INDIRECT TO FLOOR SINK.
  
 1) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-PLUMBING
 CODE 413.3 COMMERCIAL FOOD WASTE GRINDER WASTE OUTLETS.
 COMMERCIAL FOOD WASTE GRINDERS SHALL BE CONNECTED TO A
 DRAIN NOT LESS THAN 1 1/2 INCHES (38 MM) IN DIAMETER.
 COMMERCIAL FOOD WASTE GRINDERS SHALL BE CONNECTED AND
 TRAPPED SEPARATELY FROM ANY OTHER FIXTURES OR SINK
 COMPARTMENTS.
  
 TABLE 709.1 COMERCIAL FOOD WASTE GRINDERS MIN. TRAP 1
 1/2 INCHES
  
 1003.3.2 FOOD WASTE GRINDERS. WHERE FOOD WASTE GRINDERS
 CONNECT TO GREASE INTERCEPTORS, A SOLIDS INTERCEPTOR
 SHALL SEPARATE THE DISCHARGE BEFORE CONNECTING TO THE
 GREASE INTERCEPTOR. SOLIDS INTERCEPTORS AND GREASE
 INTERCEPTORS SHALL BE SIZED AND RATED FOR THE DISCHARGE
 OF THE FOOD WASTE GRINDER. EMULSIFIERS, CHEMICALS,
 ENZYMES AND BACTERIA SHALL NOT DISCHARGE INTO THE FOOD
 WASTE GRINDER.
  
 NOTE IF THE INTERCEPTOR IS NOT A HYDROMECHANICAL
 INTERCEPTOR BUT A CONCRETE VAULT THEN THE SOLIDS
 INTERCEPTOR IS NOT REQUIRED.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  