2014-02-05 07:27:46 | PLUMBING PLAN REVIEW |
| PERMIT: 14011728 |
| ADD: 2751 S DIXIE HWY |
| CONT: NORTH COUNTY PLUMBING |
| TEL: (561)625-9414 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: WED. FEB. 05/ 2014 |
| ACTION: DENIED |
| |
| SCOPE OF WORK: REPIPE COMMERCIAL DISPOSAL INTO GREASE |
| SYSTEM, INDIRECT TO FLOOR SINK. |
| |
| 1) PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-PLUMBING |
| CODE 413.3 COMMERCIAL FOOD WASTE GRINDER WASTE OUTLETS. |
| COMMERCIAL FOOD WASTE GRINDERS SHALL BE CONNECTED TO A |
| DRAIN NOT LESS THAN 1 1/2 INCHES (38 MM) IN DIAMETER. |
| COMMERCIAL FOOD WASTE GRINDERS SHALL BE CONNECTED AND |
| TRAPPED SEPARATELY FROM ANY OTHER FIXTURES OR SINK |
| COMPARTMENTS. |
| |
| TABLE 709.1 COMERCIAL FOOD WASTE GRINDERS MIN. TRAP 1 |
| 1/2 INCHES |
| |
| 1003.3.2 FOOD WASTE GRINDERS. WHERE FOOD WASTE GRINDERS |
| CONNECT TO GREASE INTERCEPTORS, A SOLIDS INTERCEPTOR |
| SHALL SEPARATE THE DISCHARGE BEFORE CONNECTING TO THE |
| GREASE INTERCEPTOR. SOLIDS INTERCEPTORS AND GREASE |
| INTERCEPTORS SHALL BE SIZED AND RATED FOR THE DISCHARGE |
| OF THE FOOD WASTE GRINDER. EMULSIFIERS, CHEMICALS, |
| ENZYMES AND BACTERIA SHALL NOT DISCHARGE INTO THE FOOD |
| WASTE GRINDER. |
| |
| NOTE IF THE INTERCEPTOR IS NOT A HYDROMECHANICAL |
| INTERCEPTOR BUT A CONCRETE VAULT THEN THE SOLIDS |
| INTERCEPTOR IS NOT REQUIRED. |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |