2014-05-06 10:28:41THE RESUBMITTAL DOES NOT ADDRESS THE COMMENTS FOR THE
 PREVIOUS DENIAL. I SPOKE W/JOSE OF CARPENTER ELECTRIC
 TO DISCUSS THE ITEMS I NEED ON THE RESUBMITTAL.
 1. DEFINE THE SCOPE OF WORK ON THE PLANS AND PERMIT.
 2. REVISE THE RISER DIAGRAM TO SHOW LOAD CALC FOR THE
 EM PANEL.
 3. SHOW RATING OF THE ATS
 4. INDICATE THE SIZE OF THE GENERATOR TO CONFIRM IT CAN
 SUSTAIN THE LOADS APPLIED.
 5, LABEL THE ROOMS ON THE SUBMITTED FLOOR PLANS.
 6. REDO THE TITLE BLOCK TO INDICATE THE JOB ADDRESS AND
 ALL REQUIRED FBC DATA. (107.2.1)