Plan Review Notes For Permit 14011702 |
Permit Number |
14011702 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-04-01 19:47:26 | THE FOLLOWING CORRECTIONS SHALL BE MADE FOR A | | SUCCESSFUL ELECTRICAL PLANS REVIEW: | | 1. DEFINE THE SCOPE OF WORK ON THE PERMIT APPLICATION. | | 2. PROVIDE PROOF OF DECLARED VALUATION | | 3. INDICATE LIGHTING COMPLIANCE AND INCLUDE ON THE | | DRAWINGS THE REQUIRED EMERGENCY AND EXIT LIGHTS. IF ANY | | WORK, BESIDES THE REQUIRED EMERGENCY & EXIT LIGHTING, | | GOES BEYOND THE SCOPE OF YOUR WORK, SO STATE, BUT THE | | EMERGENCY AND EXIT LIGHTING COMPLIANCE WILL BE ADHERED | | TO. | | 4.PERMIT APPLICATION STATES "REPAIR ELECTRICAL PANEL", | | YET THERE APPEARS TO BE 5 NEW PANELS INDICATED ON PG. | | E3 | | 5. THE NOTE BENEATH "EXISTING ELECTRICAL RISER" READS, | | "REPLACE ALL FPE PANELS" DOES THAT MEAN THAT ALL PANELS | | ARE FPE AND SHALL BE REPLACED OR DOES IT MEAN THAT ALL | | FPE PANELS WILL BE REPLACED? IF THE LATER, INDICATE | | WHICH. | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | PH: (561) 805-6718, EMAIL: [email protected] | | |
|