Plan Review Notes
Plan Review Notes For Permit 14011702
Permit Number 14011702
Review Stop E
Sequence Number 2
Notes
Date Text
2014-04-01 19:47:26THE FOLLOWING CORRECTIONS SHALL BE MADE FOR A
 SUCCESSFUL ELECTRICAL PLANS REVIEW:
 1. DEFINE THE SCOPE OF WORK ON THE PERMIT APPLICATION.
 2. PROVIDE PROOF OF DECLARED VALUATION
 3. INDICATE LIGHTING COMPLIANCE AND INCLUDE ON THE
 DRAWINGS THE REQUIRED EMERGENCY AND EXIT LIGHTS. IF ANY
 WORK, BESIDES THE REQUIRED EMERGENCY & EXIT LIGHTING,
 GOES BEYOND THE SCOPE OF YOUR WORK, SO STATE, BUT THE
 EMERGENCY AND EXIT LIGHTING COMPLIANCE WILL BE ADHERED
 TO.
 4.PERMIT APPLICATION STATES "REPAIR ELECTRICAL PANEL",
 YET THERE APPEARS TO BE 5 NEW PANELS INDICATED ON PG.
 E3
 5. THE NOTE BENEATH "EXISTING ELECTRICAL RISER" READS,
 "REPLACE ALL FPE PANELS" DOES THAT MEAN THAT ALL PANELS
 ARE FPE AND SHALL BE REPLACED OR DOES IT MEAN THAT ALL
 FPE PANELS WILL BE REPLACED? IF THE LATER, INDICATE
 WHICH.