2014-02-24 15:13:41 | PLANS CALL FOR NEW HVAC AS WELL AS OTHER ELECTRICAL | | WORK NOT ADDRESSED ON THE PERMIT APPLICATION. PLEASE | | REVISE THE PLANS TO DEFINE THE ACTUAL SCOPE OF WORK. IF | | THE SAME SHEET IS TO BE RE-SUBMITTED, MARK THE EXISTING | | AS SUCH AND INDICATE THE NEW AS NEW WORK. FURTHERMORE, | | THE SUBMITTED DRAWINGS CALL FOR WORK ON A GENERATOR NOT | | ADDRESSED ON THE PERMIT EITHER. THE HVAC CONDENSING | | UNITS DO NOT INDICATE THAT THEY COMPLY WITH NEC 210.63. | | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE | | CONTACT: | | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | PH: (561) 805-6718, EMAIL: [email protected] | | |
|