Plan Review Notes
Plan Review Notes For Permit 14011675
Permit Number 14011675
Review Stop B
Sequence Number 1
Notes
Date Text
2014-02-10 10:22:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9N-3. FOR THE FLAT ROOF SYSTEM, PROVIDE THE FLORIDA
 STATE COVER SHEET (WWW.FLORIDABUILDING.ORG, WILL SHOW
 APPROVAL NUMBER AND STATUS).
  
 2. THE FLAT ROOF SYSTEM HAS A DESIGN PRESSURE
 LIMITATION OF -72.5. PER SHEET S0.1 OF THE BUILDING
 PLANS, DP REQUIREMENTS ARE AS FOLLOWS:
  
 ZONE 1: -118.5
 ZONE 2: -186.0
 ZONE 3: -186.0
  
 PLEASE PROVIDE ALL APPLICABLE SHEETS OF THE PRODUCT
 APPROVAL WHICH INCLUDE GENERAL INFORMATION AND
 LIMITATIONS AS WELL AS INSTALLATION INSTRUCTIONS. SEE
 PAGE 5, LIMITATION 5.6, ENHANCED FASTENING IS PERMITTED
 FOR ZONES 2 AND 3 ONLY. PLEASE SELECT AN ASSEMBLY WHICH
 MEETS THE MINIMUM DP FOR ZONE 1 OF 118.5.
  
 IF ENHANCED FASTENING IS REQUIRED FOR THE NEW ASSEMBLY,
 PROVIDE ENGINEERING.
  
 3. REVIEW BY DESIGNER OF RECORD REQUIRED, FBC 107.
  
 4. THREE SETS REQUIRED AS THIS IS A THRESHOLD BUILDING,
 FBC 107.
  
  
  
  