2014-02-26 16:14:27SHEET H4.03
 MECHANICAL PROVISO; OUTSIDE AIR SUPPLY
 MECHANICAL PROVISO: 2010 FBC-ENERGY 503.2.4.4 SHUTOFF
 DAMPER CONTROLS.
 BOTH OUTDOOR AIR SUPPLY AND EXHAUST DUCTS SHALL BE
 EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN
 THE SYSTEMS OR SPACES SERVED ARE NOT IN USE.