2014-04-17 15:42:117731 SOUTH DIXIE HIGHWAY
 PERMIT #14011502
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: THE ASTM E648 TEST RESULTS (CRITICAL
 RADIANT FLUX) ARE FOR "ULTIMATE SYSTEMS LTD" FLOORING;
 HOWEVER, SHEET A6.0 STILL INDICATES "EVERLAST" AND
 "ECORE" FLOORING COMPANIES.
 ORIGINAL COMMENT - SHEET A6.0: FLOOR COVERINGS (RUBBER
 FLOORING), OTHER THAN CARPET, THAT MAY REPRESENT AN
 UNUSUAL HAZARD SHALL HAVE A CRITICAL RADIANT FLUX OF AT
 LEAST 0.1 W/CM2 (RESISTANCE TO FLAME PROPAGATION) AS
 PER NFPA 253.
  
 REPEAT COMMENT - SHEET A6.0: FINISH GB-2 INDICATES SOME
 SORT OF STYROFOAM. THE INTERIOR FINISH MATERIALS FOR
 WALLS AND CEILINGS SHALL MEET THE SMOKE DEVELOPMENT
 (0-450) AND FLAME SPREAD (76-200) REQUIREMENTS FOR
 CLASS C INTERIOR FINISHES PER NFPA 101.
  
 REPEAT COMMENT - GENERAL: PROVIDE AN EXTERIOR KEY SAFE
 TO ALLOW EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO
 THE BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN
 BE ORDERED FROM WWW.KNOXBOX.COM.
  
 REPEAT COMMENT - GENERAL: PROVIDE DRAWING NOTE
 INDICATING ALL CONSTRUCTION AND DEMOLITION WORK SHALL
 CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH AND
 CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 REPEAT COMMENT - GENERAL: PROVIDE DRAWING NOTE
 INDICATING, "FIRE PROTECTION SYSTEMS SHALL REMAIN
 ACTIVE DURING DEMOLITION AND RENOVATION ACTIVITIES. IN
 THE EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE
 FOR MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED BY EMAIL ([email protected]) OR
 IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE
 OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE
 HIGHWAY."
  
 REPEAT COMMENT - GENERAL: FOR ISSUANCE OF A GENERAL
 BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA
 BUILDING CODE REQUIRES SEALED FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF
 50 OR MORE AUTOMATIC FIRE SPRINKLERS. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730