2014-04-17 15:42:11 | 7731 SOUTH DIXIE HIGHWAY |
| PERMIT #14011502 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| RESPONSE COMMENT: THE ASTM E648 TEST RESULTS (CRITICAL |
| RADIANT FLUX) ARE FOR "ULTIMATE SYSTEMS LTD" FLOORING; |
| HOWEVER, SHEET A6.0 STILL INDICATES "EVERLAST" AND |
| "ECORE" FLOORING COMPANIES. |
| ORIGINAL COMMENT - SHEET A6.0: FLOOR COVERINGS (RUBBER |
| FLOORING), OTHER THAN CARPET, THAT MAY REPRESENT AN |
| UNUSUAL HAZARD SHALL HAVE A CRITICAL RADIANT FLUX OF AT |
| LEAST 0.1 W/CM2 (RESISTANCE TO FLAME PROPAGATION) AS |
| PER NFPA 253. |
| |
| REPEAT COMMENT - SHEET A6.0: FINISH GB-2 INDICATES SOME |
| SORT OF STYROFOAM. THE INTERIOR FINISH MATERIALS FOR |
| WALLS AND CEILINGS SHALL MEET THE SMOKE DEVELOPMENT |
| (0-450) AND FLAME SPREAD (76-200) REQUIREMENTS FOR |
| CLASS C INTERIOR FINISHES PER NFPA 101. |
| |
| REPEAT COMMENT - GENERAL: PROVIDE AN EXTERIOR KEY SAFE |
| TO ALLOW EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO |
| THE BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN |
| BE ORDERED FROM WWW.KNOXBOX.COM. |
| |
| REPEAT COMMENT - GENERAL: PROVIDE DRAWING NOTE |
| INDICATING ALL CONSTRUCTION AND DEMOLITION WORK SHALL |
| CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH AND |
| CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE |
| DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED |
| EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION |
| AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE |
| SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING |
| MATERIALS SHALL BE PROVIDED. |
| |
| REPEAT COMMENT - GENERAL: PROVIDE DRAWING NOTE |
| INDICATING, "FIRE PROTECTION SYSTEMS SHALL REMAIN |
| ACTIVE DURING DEMOLITION AND RENOVATION ACTIVITIES. IN |
| THE EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE |
| FOR MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| REQUESTS MUST BE SUBMITTED BY EMAIL ([email protected]) OR |
| IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE |
| OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE |
| HIGHWAY." |
| |
| REPEAT COMMENT - GENERAL: FOR ISSUANCE OF A GENERAL |
| BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA |
| BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| 50 OR MORE AUTOMATIC FIRE SPRINKLERS. AFTER THE |
| BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN |
| THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |