2014-04-10 14:20:2314011502
 7731 SOUTH DIXIE
 PLANET FITNESS
 2ND REVIEW
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 THE ELECTRICAL SERVICE AS NOTED ON SHEET E4.1 INDICATES
 A 600A, 277/480 VOLT SERVICE WHICH FEEDS AN EXISTING
 800A, 120/208 VOLT MDB. REVISE PLANS TO SHOW CORRECT
 VOLTAGE AND PHASE. NEC 215.5
  
 THE PLANS ARE NOT CLEAR REGARDING THE LIMITATIONS
 PROVIDED WITHIN THE CODE FOR THE NUMBER OF SERVICES
 ALLOWED TO THE BUILDING AND THE LOCATIONS OF THE MAIN
 DISCONNECTS FOR THE EXISTING AND NEW OCCUPANCIES. FIRE
 SEPARATIONS ARE ONE METHOD TO PROVIDE SEPARATION WITHIN
 STRUCTURES FOR OCCUPANCIES REQUIRING THEIR OWN ELECTRIC
 SERVICE. THE PLAN NEEDS TO VERIFY THAT THERE IS ONLY
 ONE POINT OF SERVICE TO EACH BUILDING AND THAT THE
 ELECTRICAL SERVICE MAINS FOR EACH SERVICE ARE SIX OR
 LESS AND GROUPED IN ONE LOCATION. NEC 230.2, 230.71,
 230.72
  
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE
 ALARM SYSTEMS, SECURITY AND DATA SYSTEMS.
  
  