2014-02-25 15:26:53 | PLAN DENIED | | 1) PROVIDE A DETAIL FROM THE ENGINEER ON THE | | RTU CURB TIE DOWN TO THE ROOF AND THE RTU | | TO CURB TIE DOWN. PROVIDE THE SIZE AND SPACE | | OF THE FASTENER USED. PROVIDE THE TYPE OF FASTENERS | | USED. SAME FOR CENTRIFUGAL FAN ANCHORED TO THE ROOF. | | PER SECTION 301.12 WIND RESISTANCE.2010 FBC (M) | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|