 PERMIT #14011502
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A6.0: FINISH GB-2 INDICATES SOME SORT OF
 STYROFOAM. THE INTERIOR FINISH MATERIALS FOR WALLS AND
 CEILINGS SHALL MEET THE SMOKE DEVELOPMENT (0-450) AND
 FLAME SPREAD (76-200) REQUIREMENTS FOR CLASS C INTERIOR
 FINISHES PER NFPA 101.
  
 SHEET A6.0: FLOOR COVERINGS (RUBBER FLOORING), OTHER
 THAN CARPET, THAT MAY REPRESENT AN UNUSUAL HAZARD SHALL
 HAVE A CRITICAL RADIANT FLUX OF AT LEAST 0.1 W/CM2
 (RESISTANCE TO FLAME PROPAGATION) AS PER NFPA 253.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING ALL
 CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING, "FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: FOR ISSUANCE OF A GENERAL BUILDING PERMIT,
 SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING CODE
 REQUIRES SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS
 FOR THE DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC
 FIRE SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN
 ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  