2014-02-05 10:37:2414011502
 7731 SOUTH DIXIE
 PLANET FITNESS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.22, 110.16, 110.22
  
 PROVIDE DIMENSIONS FOR THE DESIGNATED CLEAR WORKING
 SPACES REQUIRED AROUND THE ELECTRICAL SERVICE EQUIPMENT
 AND PANEL BOARDS. NEC 215.5, 110.26
  
 VERIFY THE EXISTING ELECTRICAL MDP HAS A FAULT CURRENT
 RATING THAT IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE
 FOR THE CURRENT THAT MUST BE INTERRUPTED. NEC 110.9
  
 VERIFY THE REQUIRED GFCI PROTECTED RECEPTACLE IS
 AVAILABLE TO SERVICE ROOF TOP MECHANICAL EQUIPMENT. NEC
 210.8(B)
 PROVIDE A STRUCTURAL DETAIL FOR HANGING THE B.A. FANS
 AND TVS FROM THE EXISTING STRUCTURE. FBC 1604.1
  
 PROVIDE A KEY PLAN SHOWING OCCUPANCY LOCATION WITH
 ADJACENT TENANTS. INDICATE LOCATION OF ALL EXISTING OR
 PROPOSED ELECTRICAL SERVICES WITH MAIN DISCONNECTS
 SERVING THE PLAZA. NEC 230.2, 230.7
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR, FIRE
 ALARM, SECURITY AND DATA SYSTEMS.
  