Notes |
Date |
Text |
2014-01-27 09:57:00 | PLUMBING PROVISO: | | AIR ADMITTANCE VALVE ON KITCHEN SINK: | | 917.3.2 RELIEF VENT. | | WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR | | BRANCH INTERVALS FROM THE TOP OF THE STACK, | | THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF | | VENT THAT SHALL CONNECT TO A VENT STACK OR | | STACK VENT, OR EXTEND OUTDOORS TO THE OPEN AIR. THE | | RELIEF VENT SHALL CONNECT TO THE HORIZONTAL BRANCH | | DRAIN BETWEEN THE STACK AND THE MOST DOWNSTREAM FIXTURE | | DRAIN CONNECTED TO THE HORIZONTAL BRANCH | | DRAIN. THE RELIEF VENT SHALL BE SIZED IN ACCORDANCE | | WITH SECTION 916.2 AND INSTALLED IN ACCORDANCE WITH | | SECTION 905. THE RELIEF VENT SHALL BE PERMITTED TO | | SERVE AS THE VENT FOR OTHER FIXTURES. |
|