Plan Review Notes
Plan Review Notes For Permit 14011465
Permit Number 14011465
Review Stop P
Sequence Number 1
Notes
Date Text
2014-01-27 09:57:00PLUMBING PROVISO:
 AIR ADMITTANCE VALVE ON KITCHEN SINK:
 917.3.2 RELIEF VENT.
 WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK,
 THE HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF
 VENT THAT SHALL CONNECT TO A VENT STACK OR
 STACK VENT, OR EXTEND OUTDOORS TO THE OPEN AIR. THE
 RELIEF VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 DRAIN BETWEEN THE STACK AND THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTED TO THE HORIZONTAL BRANCH
 DRAIN. THE RELIEF VENT SHALL BE SIZED IN ACCORDANCE
 WITH SECTION 916.2 AND INSTALLED IN ACCORDANCE WITH
 SECTION 905. THE RELIEF VENT SHALL BE PERMITTED TO
 SERVE AS THE VENT FOR OTHER FIXTURES.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved