2014-10-21 13:39:37 | 1)SHT. S.2 - DETAILS #1 & 2 - THE MEASUREMENT FROM THE |
| FINISHED FLOOR TO THE TOP OF THE WATER CLOSET SEAT |
| SHALL BE 17' - 19" PER THE 2010 FL. ACCESSIBILITY CODE |
| SEC.604.4. |
| 2) THE HEIGHT OF THE RIM OF THE LAVATORY TO THE |
| FINISHED FLOR SHALL BE A MAX. OF 34". SHOW THIS ON THE |
| PLAN. |
| 3) SHOW THE DIMENSION FROM THE FINISHED FLOOR TO THE |
| BOTTOM OF THE MIRROR. COMPLY W/ FAC SEC. 603.3. |
| 4) SUBMIT CALCULATIONS FOR THE SIZING OF THE GREASE |
| TRAP. COMPLY W/ FPC SEC.103.3.4. |
| 5) THE CLEANOUT FOR THE GREASE TRAP IS INSTALLED IN THE |
| OPPOSITE DIRECTION OF FLOW. |
| 6) SHT. P.4 - THE SERVICE SINK IS LISTED ON THE |
| SANITARY ISER ISOMETRIC AS "EXISTING" BUT THE PLAN |
| SHOWS IT AS NEW. CLARIFY. |
| 7) THE SERVICE SINK SHALL NOT BE MORE THAN 12 FT. FROM |
| A VENTED LINE PER TABLE 906.1. |
| 8) A DRINKING FOUNTAIN IS REQD. PER TABLE 403.1. YOU |
| HAVE LISTED AN OCCUPANT LOAD OF 69 PERSONS SO THE |
| EXCEPTION IN FOOTNOTE F DOES NOT APPLY. |
| 9) SHT. P.4 - SHOWS THE GREASE TRAP TO BE OF CONCRETE |
| BUT THE SPECS ARE FOR A METAL TANK. CLARIFY. SUBMIT |
| MANUF. SPECIFICATIONS FOR THE GREASE INTERCEPTOR TO BE |
| USED. |
| 10) SHT. P.5 SHOWS THE RELIEF LINE DISCHARGING TO A |
| FLOOR DRAIN BUT THERE IS NO FLOOR DRAIN IN THIS AREA. |
| CLARIFY. |
| 11) YOU ARE CLASSIFYING THIS AS AN A-2 OCCUPANCY? HOW |
| CAN THIS BE? THIS APPEARS TO BE MORE OF A MERCANTILE |
| OCCUPANCY THAN AN ASSEMBLY. CLARIFY. |
| |
| |