Plan Review Notes
Plan Review Notes For Permit 14011422
Permit Number 14011422
Review Stop G
Sequence Number 4
Notes
Date Text
2014-10-21 12:17:341) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE GAS
 APPLIANCES IN COMPLIANCE WITH THE 2010 FUEL GAS CODE
 SEC.304.
 2) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 AND TERMINATION POINTS OF ALL GAS VENTS.2010 FGC SECS.
 502 THRU 505.
 3) SUBMIT MANUFACTURER'S SPEC. SHEETS FOR ALL GAS
 EQUIPMENT.EQUIPMENT SHALL BE LISTED AND LABELED PER THE
 2010 FGC SEC. 301.3.
 4) COMMERCIAL COOKING APPLIANCE VENTING SHALL COMPLY
 W/2010 FGC SEC.623.6, AND 505.1.1.