2014-07-28 08:03:40 | PLUMBNG PLAN REVIEW |
| PERMIT: 14011422 |
| ADD: 847 SOUTHERN BLVD. |
| CONT: CARLOS GONZALEZ |
| TEL: (561)386-8217 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 3RD REVIEW |
| DATE: MON. JULY 28/2014 |
| ACTION: DENIED |
| |
| 1) 3RD REQUEST. 2010 WEST PALM BEACH AMENDMENTS TO THE |
| FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1.3 PLUMBING |
| 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT |
| LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 PLEASE |
| NOTE THE SERVICE SINK ON THE EXTERIOR OF THE BUILDING |
| WILL NEED TO SHOW TYING INTO THE GREASY WASTE BEFOR THE |
| GREASE INTERCEPTOR. THIS INFORMATION WAS ON THE PLANS |
| SUBMITTED |
| 4/ 09/14 BY THE DESIGNER OF RECORD, NOW IT IS MISSING. |
| |
| 2) 3RD REQUEST. . THE LAST SET OF PLANS REVIEW # 2 |
| LISTED BY NUMBER, (1,2,3,4,5,6,...) SHEET 3 OF 4 |
| INDICATES EITHER FIXTURES OR APPLIANCES 1-17, THE PLANS |
| DO NOT IDENTIFY IF THESE ARE FIXTURES REQUIRING FLOOR |
| SINKS (THREE COMPARTMENT SINK, HAND SINK, REFRIGARATED |
| CASES, ICE MAKING MACHINES, COFFE URNS, AND DRINK |
| DISPENSORS. THEY ARE NOT IDENTIFIED. NOW THE NUMBERS |
| ARE TOTALLY MISSING AND THE USE OF THESE FIXTURES AND |
| OR APPLIANCES: |
| 2010 FBC-P 802.1 WHERE REQUIRED. |
| FOOD-HANDLING EQUIPMENT AND CLEAR-WATER WASTE SHALL |
| DISCHARGE THROUGH AN INDIRECT WASTE PIPE AS SPECIFIED |
| IN SECTIONS 802.1.1 THROUGH 802.1.8. ALL HEALTH-CARE |
| RELATED FIXTURES, DEVICES AND EQUIPMENT SHALL DISCHARGE |
| TO THE DRAINAGE SYSTEM THROUGH AN INDIRECT WASTE PIPE |
| BY MEANS OF AN AIR GAP IN ACCORDANCE WITH THIS CHAPTER |
| AND SECTION 713.3. FIXTURES NOT REQUIRED BY THIS |
| SECTION TO BE INDIRECTLY CONNECTED SHALL BE DIRECTLY |
| CONNECTED TO THE PLUMBING SYSTEM IN ACCORDANCE WITH |
| CHAPTER 7. |
| |
| 802.1.1 FOOD HANDLING. |
| EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE, |
| PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE |
| THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. |
| . |
| |
| 3. WATER SUPPLY PIPING, THE ISSUE WITH THIS PLAN IS ON |
| THE POTABLE WATER SUPPLY ICE MAKING MACHINES, COFFE |
| URNS, AND DRINK DISPENSORS. |
| 2010 FBC-P 608.16.1 BEVERAGE DISPENSERS. THE WATER |
| SUPPLY CONNECTION TO BEVERAGE DISPENSERS SHALL BE |
| PROTECTED AGAINST BACKFLOW BY A BACKFLOW PREVENTER |
| CONFORMING TO ASSE 1022 OR BY AN AIR GAP.THE PORTION OF |
| THE BACKFLOW PREVENTER DEVICE DOWNSTREAM FROM THE |
| SECOND CHECK VALVE AND THE PIPING DOWNSTREAM THEREFROM |
| SHALL NOT BE AFFECTED BY CARBON DIOXIDE GAS. |
| |
| |
| |
| 4. 3RD REQUEST - SANITARY DRAINAGE THE ISOMETRIC |
| DRAWING SHOWS THE HAND SINKS AND 3 COMPARTMENT SINKS |
| WITH A DIRECT CONNECTION TO THE WASTE NO FLOOR SINK FOR |
| A INDIRECT CONNECTION 802.1.1, THE OTHER ISSUE WITH THE |
| PLANS IS NO INDIVIDUAL DRAINS ARE SHOWN AS DRAWN, FOR |
| THE FLOOR SINKS, VENTS WILL NEED TO BE ILLUSTRATED. |
| FLOOR DRAIN IN THE KITCHEN WILL NEED A TRAP PRIMER |
| SINCE IT IS NOT BEING FED BY A FIXTURE (1002.4 TRAP |
| SEALS), |
| THE HAND SINK THAT BACKS UP TO THE STORAGE ROOM SHOULD |
| NOT BE ON THE GREASY WASTE (P 1003.3.1), AGAIN THE |
| SERVICE SINK ON THE EXTERIOR OF THE BUILDING IS NOT |
| PART OF THE GREASY WASTE. IF THIS FIXTURE IS A CAN WASH |
| IT TO SHOULD BE ON THE GREASY WASTE AND THE REQUIREMENT |
| FOR A SERVICE |
| SINK WILL STILL NEED TO BE MET. TABLE 403. USE A2 |
| RESTARAUNT/ DELI. |
| |
| |
| 5.COMPLIED. WATER HEATERS |
| |
| 6. 3RD REQUEST THE FLOOR SINK, NOT SHOWN FOR THE 3 |
| COMPARTMENT SINK WILL NEED TO BE VENTED, THE FLOW |
| CONTROL FOR THE GREASE INTERCEPTOR WILL ALSO NEED TO BE |
| VENTED, SEE INDIVIDUAL VENTS 607.1 & 1003.3.4.2. |
| |
| 7). 3RD BACK FLOW PREVENTION 608.3 DEVICES, |
| APPURTENANCES, APPLIANCES AND APPARATUS. ALL DEVICES, |
| APPURTENANCES, APPLIANCES AND APPARATUS INTENDED TO |
| SERVE SOME SPECIAL FUNCTION, COOLING, OR STORAGE OF ICE |
| OR FOODS, |
| |
| 8) 3RD 604.9 WATER HAMMER. THE FLOW VELOCITY OF THE |
| WATER DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE |
| THE POSSIBILITY OF WATER HAMMER. A WATER-HAMMER |
| ARRESTOR SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES |
| ARE UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS. |
| WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010 |
| |
| 9. 3RD PLUMBING RISER MISSING FLOOR SINKS FBC-P 802.1. |
| 8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. SINKS |
| USED FOR THE WASHING, RINSING OR SANITIZING OF |
| UTENSILS, DISHES, POTS, PANS OR SERVICEWARE USED IN THE |
| PREPARATION, SERVING OR EATING OF FOOD SHALL DISCHARGE |
| INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK OR |
| DIRECTLY CONNECT TO THE DRAINAGE SYSTEM. |
| |
| 802.1.7 COMMERCIAL DISHWASHING MACHINES. |
| THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE |
| SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A |
| STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION |
| 802.2. |
| |
| 802.1.5 NONPOTABLE CLEAR-WATER WASTE. |
| WHERE DEVICES AND EQUIPMENT SUCH AS PROCESS TANKS, |
| FILTERS, DRIPS AND BOILERS DISCHARGE NONPOTABLE WATER |
| TO THE BUILDING DRAINAGE SYSTEM, THE DISCHARGE SHALL BE |
| THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR BREAK |
| OR AN AIR GAP. |
| |
| 10) 3RD REQUET THE GREASE INTERCEPTOR IS NOW INDICATED |
| AS A 750 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR. |
| CONCRETE VAULT INTERCEPTORS ARE |
| SIZED BY USING THE FOLLOWING 2010 FBC-P 1003.5.1. |
| PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION SHOWING |
| COMPLIANCE WITH 1003.3.5. |
| |
| 2ND GREASE INTERCEPTOR SHEET 2 INDICATES THE USE OF A |
| ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE |
| MANUFACTURERS SPECS ON THIS UNIT. |
| PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE |
| METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC |
| GREASE REMOVAL DEVICES. |
| THE GREASY WASTE SHOULD ALSO INCLUDE THE FLOOR DRAIN |
| AND SERVIDE SINK/ MOP SINK. |
| THE PLANS DO NOT INCLUDE THE LOCATION OF THE GREASE |
| INTERCEPTOR. |
| |
| GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE |
| INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS |
| AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |