Plan Review Notes
Plan Review Notes For Permit 14011422
Permit Number 14011422
Review Stop P
Sequence Number 3
Notes
Date Text
2014-07-28 08:03:40PLUMBNG PLAN REVIEW
 PERMIT: 14011422
 ADD: 847 SOUTHERN BLVD.
 CONT: CARLOS GONZALEZ
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JULY 28/2014
 ACTION: DENIED
  
 1) 3RD REQUEST. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT
 LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 PLEASE
 NOTE THE SERVICE SINK ON THE EXTERIOR OF THE BUILDING
 WILL NEED TO SHOW TYING INTO THE GREASY WASTE BEFOR THE
 GREASE INTERCEPTOR. THIS INFORMATION WAS ON THE PLANS
 SUBMITTED
 4/ 09/14 BY THE DESIGNER OF RECORD, NOW IT IS MISSING.
  
 2) 3RD REQUEST. . THE LAST SET OF PLANS REVIEW # 2
 LISTED BY NUMBER, (1,2,3,4,5,6,...) SHEET 3 OF 4
 INDICATES EITHER FIXTURES OR APPLIANCES 1-17, THE PLANS
 DO NOT IDENTIFY IF THESE ARE FIXTURES REQUIRING FLOOR
 SINKS (THREE COMPARTMENT SINK, HAND SINK, REFRIGARATED
 CASES, ICE MAKING MACHINES, COFFE URNS, AND DRINK
 DISPENSORS. THEY ARE NOT IDENTIFIED. NOW THE NUMBERS
 ARE TOTALLY MISSING AND THE USE OF THESE FIXTURES AND
 OR APPLIANCES:
 2010 FBC-P 802.1 WHERE REQUIRED.
 FOOD-HANDLING EQUIPMENT AND CLEAR-WATER WASTE SHALL
 DISCHARGE THROUGH AN INDIRECT WASTE PIPE AS SPECIFIED
 IN SECTIONS 802.1.1 THROUGH 802.1.8. ALL HEALTH-CARE
 RELATED FIXTURES, DEVICES AND EQUIPMENT SHALL DISCHARGE
 TO THE DRAINAGE SYSTEM THROUGH AN INDIRECT WASTE PIPE
 BY MEANS OF AN AIR GAP IN ACCORDANCE WITH THIS CHAPTER
 AND SECTION 713.3. FIXTURES NOT REQUIRED BY THIS
 SECTION TO BE INDIRECTLY CONNECTED SHALL BE DIRECTLY
 CONNECTED TO THE PLUMBING SYSTEM IN ACCORDANCE WITH
 CHAPTER 7.
  
 802.1.1 FOOD HANDLING.
 EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE,
 PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
 .
  
 3. WATER SUPPLY PIPING, THE ISSUE WITH THIS PLAN IS ON
 THE POTABLE WATER SUPPLY ICE MAKING MACHINES, COFFE
 URNS, AND DRINK DISPENSORS.
 2010 FBC-P 608.16.1 BEVERAGE DISPENSERS. THE WATER
 SUPPLY CONNECTION TO BEVERAGE DISPENSERS SHALL BE
 PROTECTED AGAINST BACKFLOW BY A BACKFLOW PREVENTER
 CONFORMING TO ASSE 1022 OR BY AN AIR GAP.THE PORTION OF
 THE BACKFLOW PREVENTER DEVICE DOWNSTREAM FROM THE
 SECOND CHECK VALVE AND THE PIPING DOWNSTREAM THEREFROM
 SHALL NOT BE AFFECTED BY CARBON DIOXIDE GAS.
  
  
  
 4. 3RD REQUEST - SANITARY DRAINAGE THE ISOMETRIC
 DRAWING SHOWS THE HAND SINKS AND 3 COMPARTMENT SINKS
 WITH A DIRECT CONNECTION TO THE WASTE NO FLOOR SINK FOR
 A INDIRECT CONNECTION 802.1.1, THE OTHER ISSUE WITH THE
 PLANS IS NO INDIVIDUAL DRAINS ARE SHOWN AS DRAWN, FOR
 THE FLOOR SINKS, VENTS WILL NEED TO BE ILLUSTRATED.
 FLOOR DRAIN IN THE KITCHEN WILL NEED A TRAP PRIMER
 SINCE IT IS NOT BEING FED BY A FIXTURE (1002.4 TRAP
 SEALS),
 THE HAND SINK THAT BACKS UP TO THE STORAGE ROOM SHOULD
 NOT BE ON THE GREASY WASTE (P 1003.3.1), AGAIN THE
 SERVICE SINK ON THE EXTERIOR OF THE BUILDING IS NOT
 PART OF THE GREASY WASTE. IF THIS FIXTURE IS A CAN WASH
 IT TO SHOULD BE ON THE GREASY WASTE AND THE REQUIREMENT
 FOR A SERVICE
 SINK WILL STILL NEED TO BE MET. TABLE 403. USE A2
 RESTARAUNT/ DELI.
  
  
 5.COMPLIED. WATER HEATERS
  
 6. 3RD REQUEST THE FLOOR SINK, NOT SHOWN FOR THE 3
 COMPARTMENT SINK WILL NEED TO BE VENTED, THE FLOW
 CONTROL FOR THE GREASE INTERCEPTOR WILL ALSO NEED TO BE
 VENTED, SEE INDIVIDUAL VENTS 607.1 & 1003.3.4.2.
  
 7). 3RD BACK FLOW PREVENTION 608.3 DEVICES,
 APPURTENANCES, APPLIANCES AND APPARATUS. ALL DEVICES,
 APPURTENANCES, APPLIANCES AND APPARATUS INTENDED TO
 SERVE SOME SPECIAL FUNCTION, COOLING, OR STORAGE OF ICE
 OR FOODS,
  
 8) 3RD 604.9 WATER HAMMER. THE FLOW VELOCITY OF THE
 WATER DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE
 THE POSSIBILITY OF WATER HAMMER. A WATER-HAMMER
 ARRESTOR SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES
 ARE UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010
  
 9. 3RD PLUMBING RISER MISSING FLOOR SINKS FBC-P 802.1.
 8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. SINKS
 USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICEWARE USED IN THE
 PREPARATION, SERVING OR EATING OF FOOD SHALL DISCHARGE
 INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK OR
 DIRECTLY CONNECT TO THE DRAINAGE SYSTEM.
  
 802.1.7 COMMERCIAL DISHWASHING MACHINES.
 THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE
 SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2.
  
 802.1.5 NONPOTABLE CLEAR-WATER WASTE.
 WHERE DEVICES AND EQUIPMENT SUCH AS PROCESS TANKS,
 FILTERS, DRIPS AND BOILERS DISCHARGE NONPOTABLE WATER
 TO THE BUILDING DRAINAGE SYSTEM, THE DISCHARGE SHALL BE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR BREAK
 OR AN AIR GAP.
  
 10) 3RD REQUET THE GREASE INTERCEPTOR IS NOW INDICATED
 AS A 750 GALLON CONCRETE VAULT TYPE GREASE INTERCEPTOR.
 CONCRETE VAULT INTERCEPTORS ARE
 SIZED BY USING THE FOLLOWING 2010 FBC-P 1003.5.1.
 PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION SHOWING
 COMPLIANCE WITH 1003.3.5.
  
 2ND GREASE INTERCEPTOR SHEET 2 INDICATES THE USE OF A
 ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE
 MANUFACTURERS SPECS ON THIS UNIT.
 PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE
 METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES.
 THE GREASY WASTE SHOULD ALSO INCLUDE THE FLOOR DRAIN
 AND SERVIDE SINK/ MOP SINK.
 THE PLANS DO NOT INCLUDE THE LOCATION OF THE GREASE
 INTERCEPTOR.
  
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO