Plan Review Notes For Permit 14011422 |
Permit Number |
14011422 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2014-07-10 10:13:29 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1. ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY | | WITH NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE | | PROTECTION OF COMMERCIAL COOKING OPERATIONS. | | EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS | | SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. | | | | COOKING OPERATIONS PRODUCING SMOKE OR GREASE-LADEN | | VAPORS SHALL BE PROTECTED WITH A CLASS I MECHANICAL | | EXHAUST HOOD EQUIPPED WITH AN AUTOMATIC WET-CHEMICAL | | FIRE SUPPRESSION | | SYSTEM. | | | | A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG THE | | EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A MAXIMUM | | OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE DEVICE | | SHALL BE | | MOUNTED 42-48 INCHES ABOVE THE FLOOR AND SHALL CLEARLY | | IDENTIFY THE HAZARD PROTECTED. | | | | PROVIDE A K-TYPE PORTABLE FIRE EXTINGUISHER AND | | ASSOCIATED SIGNAGE IN KITCHEN AREA. | | | | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE | | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE | | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT | | TEMPERATURE REACHES 475F | | DEGREES AT 1-INCH BELOW THE SURFACE. | | | | PROVIDE AN 8? TALL STEEL BAFFLE OR PROVIDE 16? OF SPACE | | BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE | | ADJACENT EQUIPMENT. | | | | | | |
|