Date |
Text |
2014-04-22 17:25:49 | PLUMBNG PLAN REVIEW |
| PERMIT: 14011422 |
| ADD: 847 SOUTHERN BLVD. |
| CONT: CARLOS GONZALEZ |
| TEL: (561)386-8217 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. APRIL 22/2014 |
| ACTION: DENIED |
| |
| 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: PROVIDE A COMPLETE |
| FLOOR PLAN OF THE BUILDING AND ENTENDED USAGE. |
| THE EXAMINATION OF THE DOCUMENTS BY THE |
| BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM |
| CRITERIA AND DOCUMENTS: |
| 107.3.5.1.3 PLUMBING |
| 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT |
| LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 PLEASE |
| NOTE THE SERVICE SINK ON THE EXTERIOR OF THE BUILDING |
| WILL NEED TO SHOW TYING INTO THE GREASY WASTE BEFOR THE |
| GREASE INTERCEPTOR. |
| 2. FIXTURE REQUIREMENTS SHEET 3 OF 4 INDICATES EITHER |
| FIXTURES OR APPLIANCES 1-17, THE PLANS DO NOT IDENTIFY |
| IF THESE ARE FIXTURES REQUIRING FLOOR SINKS (THREE |
| COMPARTMENT SINK, HAND SINK, REFRIGARATED CASES, ICE |
| MAKING MACHINES, COFFE URNS, AND DRINK DISPENSORS. 2010 |
| FBC-P 802.1.1. |
| 3.COMPLIED. WATER SUPPLY PIPING |
| 4. 2ND REQUEST - SANITARY DRAINAGE THE ISOMETRIC |
| DRAWING SHOWS THE HAND SINKS AND 2 COMPARTMENT SINKS |
| WITH A DIRECT CONNECTION TO THE WASTE NO FLOOR SINK FOR |
| A INDIRECT CONNECTION 802.1.1, THE OTHER ISSUE WITH THE |
| PLANS IS NO INDIVIDUAL DRAINS ARE SHOWN AS DRAWN, FOR |
| THE FLOOR SINKS VENTS WILL NEED TO BE ILLUSTRATED. |
| FLOOR DRAIN IN THE KITCHEN WILL NEED A TRAP PRIMER |
| SINCE IT IS NOT BEING FED BY A FIXTURE (1002.4 TRAP |
| SEALS), |
| 5.COMPLIED. WATER HEATERS |
| 6. VENTS AS DRAWN NOW THE 3 COMPARTMENT SINK, AND ALL |
| HAND SINKS ARE BEING VENTED BY A SINGLE VENT , THE |
| FLOOR SINKS WILL NEED TO BE VENTED, THE FLOW CONTROL |
| FOR THE GREASE INTERCEPTOR WILL ALSO NEED TO BE VENTED, |
| SEE INDIVIDUAL VENTS 607.1 & 1003.3.4.2. |
| 7). BACK FLOW PREVENTION 608.3 DEVICES, APPURTENANCES, |
| APPLIANCES AND APPARATUS. ALL DEVICES, APPURTENANCES, |
| APPLIANCES AND APPARATUS INTENDED TO SERVE SOME SPECIAL |
| FUNCTION, COOLING, OR STORAGE OF ICE OR FOODS, |
| 8) 604.9 WATER HAMMER. THE FLOW VELOCITY OF THE WATER |
| DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE THE |
| POSSIBILITY OF WATER HAMMER. A WATER-HAMMER ARRESTOR |
| SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE |
| UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS. |
| WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010 |
| 9. CORRECTED PLUMBING RISER |
| |
| 2) 2ND REQUEST GREASE INTERCEPTOR SHEET 2 INDICATES THE |
| USE OF A ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE |
| MANUFACTURERS SPECS ON THIS UNIT. |
| PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE |
| METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC |
| GREASE REMOVAL DEVICES. |
| THE GREASY WASTE SHOULD ALSO INCLUDE THE FLOOR DRAIN |
| AND SERVIDE SINK/ MOP SINK. |
| THE PLANS DO NOT INCLUDE THE LOCATION OF THE GREASE |
| INTERCEPTOR. |
| |
| GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE |
| INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS |
| AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |