Plan Review Notes
Plan Review Notes For Permit 14011422
Permit Number 14011422
Review Stop P
Sequence Number 2
Notes
Date Text
2014-04-22 17:25:49PLUMBNG PLAN REVIEW
 PERMIT: 14011422
 ADD: 847 SOUTHERN BLVD.
 CONT: CARLOS GONZALEZ
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. APRIL 22/2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: PROVIDE A COMPLETE
 FLOOR PLAN OF THE BUILDING AND ENTENDED USAGE.
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT
 LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 PLEASE
 NOTE THE SERVICE SINK ON THE EXTERIOR OF THE BUILDING
 WILL NEED TO SHOW TYING INTO THE GREASY WASTE BEFOR THE
 GREASE INTERCEPTOR.
 2. FIXTURE REQUIREMENTS SHEET 3 OF 4 INDICATES EITHER
 FIXTURES OR APPLIANCES 1-17, THE PLANS DO NOT IDENTIFY
 IF THESE ARE FIXTURES REQUIRING FLOOR SINKS (THREE
 COMPARTMENT SINK, HAND SINK, REFRIGARATED CASES, ICE
 MAKING MACHINES, COFFE URNS, AND DRINK DISPENSORS. 2010
 FBC-P 802.1.1.
 3.COMPLIED. WATER SUPPLY PIPING
 4. 2ND REQUEST - SANITARY DRAINAGE THE ISOMETRIC
 DRAWING SHOWS THE HAND SINKS AND 2 COMPARTMENT SINKS
 WITH A DIRECT CONNECTION TO THE WASTE NO FLOOR SINK FOR
 A INDIRECT CONNECTION 802.1.1, THE OTHER ISSUE WITH THE
 PLANS IS NO INDIVIDUAL DRAINS ARE SHOWN AS DRAWN, FOR
 THE FLOOR SINKS VENTS WILL NEED TO BE ILLUSTRATED.
 FLOOR DRAIN IN THE KITCHEN WILL NEED A TRAP PRIMER
 SINCE IT IS NOT BEING FED BY A FIXTURE (1002.4 TRAP
 SEALS),
 5.COMPLIED. WATER HEATERS
 6. VENTS AS DRAWN NOW THE 3 COMPARTMENT SINK, AND ALL
 HAND SINKS ARE BEING VENTED BY A SINGLE VENT , THE
 FLOOR SINKS WILL NEED TO BE VENTED, THE FLOW CONTROL
 FOR THE GREASE INTERCEPTOR WILL ALSO NEED TO BE VENTED,
 SEE INDIVIDUAL VENTS 607.1 & 1003.3.4.2.
 7). BACK FLOW PREVENTION 608.3 DEVICES, APPURTENANCES,
 APPLIANCES AND APPARATUS. ALL DEVICES, APPURTENANCES,
 APPLIANCES AND APPARATUS INTENDED TO SERVE SOME SPECIAL
 FUNCTION, COOLING, OR STORAGE OF ICE OR FOODS,
 8) 604.9 WATER HAMMER. THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED TO REDUCE THE
 POSSIBILITY OF WATER HAMMER. A WATER-HAMMER ARRESTOR
 SHALL BE INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S SPECIFICATIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010
 9. CORRECTED PLUMBING RISER
  
 2) 2ND REQUEST GREASE INTERCEPTOR SHEET 2 INDICATES THE
 USE OF A ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE
 MANUFACTURERS SPECS ON THIS UNIT.
 PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE
 METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES.
 THE GREASY WASTE SHOULD ALSO INCLUDE THE FLOOR DRAIN
 AND SERVIDE SINK/ MOP SINK.
 THE PLANS DO NOT INCLUDE THE LOCATION OF THE GREASE
 INTERCEPTOR.
  
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved