Plan Review Notes
Plan Review Notes For Permit 14011422
Permit Number 14011422
Review Stop M
Sequence Number 2
Notes
Date Text
2014-05-13 10:54:17PLAN DENIED
 1) PROVIDE THE GAGE OF STRAP AN SIZE
 AND TYPE OF ANCHOR USED TO TIE DOWN
 CONDENSER. PER SECTION 301.12 WIND RESISTANCE
 2010 FBC (M)
 2) PROVIDE ENERGY CALCULATION WITH PLAN
 PER 503.2.1 CALCULATION OF HEATING AND
 COOLING LOADS FLORIDA ENERGY CODE
 3) PROVIDE CFM ON ALL SUPPLY GRILLS.
 PROVIDE EQUIPMENT SCHEDULE ON THE PLAN.
 PER SECTION 107 FBC
 4) HOOD REQUIRES SEPARATE APPLICATION, COMPLETE
 SET OF PLANS AND PERMIT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  