2014-04-24 13:47:24 | 847 SOUTHERN BOULEVARD |
| PERMIT #14011422 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NEW COMMENT - SHEET 4 OF 4: PROVIDE A DISPLAY LAYOUT OF |
| THE NEW AND EXISTING "DISPLAY ROOMS" SHOWING AISLE |
| WIDTHS, SHELVING, SEATING, ETC. |
| |
| REVIEW #2 COMMENT - SHEET 4 OF 4: NO FIRE RATED DOOR |
| SHOWN ON EXISTING STORAGE ROOM. |
| ORIGINAL COMMENT: PER SECTION 8.7, ANY AREA (STORAGE) |
| HAVING A DEGREE OF HAZARD GREATER THAN NORMAL TO THE |
| GENERAL OCCUPANCY (MERCANTILE) OF THE BUILDING, SHALL |
| BE SEPARATED FROM NON-STORAGE AREAS WITH A 1-HOUR |
| FIRE-RATED BARRIER OR BE PROTECTED WITH AN AUTOMATIC |
| SPRINKLER SYSTEM. DOORS SHALL BE SELF CLOSING, POSITIVE |
| LATCHING, AND FIRE-RATED FOR AT LEAST 45-MINUTES. |
| |
| REPEAT COMMENT: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED |
| EXIT DOORS WITH EXIT SIGNS. |
| |
| REPEAT COMMENT: PER SECTION 7.2.1.5.9, THE LOCK/LATCH |
| RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR |
| WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| TO OPERATE. THUMB-TURN LOCK TO BE EQUIPPED WITH AN |
| "OPEN/LOCKED" INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 |
| OR SIMILAR). |
| |
| |