2014-02-27 14:57:07 | PLUMBNG PLAN REVIEW |
| PERMIT: 14011422 |
| ADD: 847 SOUTHERN BLVD. |
| CONT: CARLOS GONZALEZ |
| TEL: (561)386-8217 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. FEB.27/ 2014 |
| ACTION: DENIED |
| |
| 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: PROVIDE A COMPLETE |
| FLOOR PLAN OF THE BUILDING AND ENTENDED USAGE. |
| THE EXAMINATION OF THE DOCUMENTS BY THE |
| BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM |
| CRITERIA AND DOCUMENTS: |
| 107.3.5.1.3 PLUMBING |
| 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT |
| LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1 |
| 2. FIXTURE REQUIREMENTS |
| 3. WATER SUPPLY PIPING |
| 4. SANITARY DRAINAGE |
| 5. WATER HEATERS |
| 6. VENTS |
| 78. BACK FLOW PREVENTION |
| 9. LOCATION OF WATER SUPPLY LINE |
| 10. GREASE TRAPS |
| 11 PLUMBING RISER |
| |
| 2) GREASE INTERCEPTOR SHEET 2 INDICATES THE USE OF A |
| ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE |
| MANUFACTURERS SPECS ON THIS UNIT. |
| PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE |
| METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC |
| GREASE REMOVAL DEVICES. |
| GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL |
| DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE |
| INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL |
| BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101, |
| ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS |
| AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED |
| IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS. |
| EXCEPTION: GREASE INTERCEPTORS THAT ARE SIZED, |
| CONSTRUCTED AND APPROVED IN ACCORDANCE WITH RULE 64E-6, |
| FLORIDA ADMINISTRATIVE CODE AND THAT ARE LOCATED |
| OUTSIDE THE BUILDING SHALL NOT BE REQUIRED TO MEET THE |
| REQUIREMENTS OF THIS SECTION. |
| |
| 3) PROVIDE THE LOCATION OF THE GREASE INTERCEPTOR ON |
| THE PLANS. |
| |
| 4) ALSO PROVIDE THE FLOW CONTROL DEVICE WITH THE |
| MANUFACTURERS INSTRUCTIONS AND SHOW THE REQUIRED VENT |
| FOR THE FLOW CONTROL. |
| |
| 5) THE PLANS DO NOT INDICATE A DISHWASHER OR FOOD |
| GRINDER, WILL THERE BE EITHER ONE OR BOTH, THEY WILL |
| AFFECT CALCULATIOSN FOR THE AUTOMATIC GREASE REMOVAL |
| DEVICE. |
| |
| 6) PLANS DO NOT INDICATE A FLOOR SINK / MOP SINK PART |
| OF THE REQUIEMENTS PLUMBING TABLE 403.1 A2 REQUIREMENT, |
| EVEN THOUGH THIS MAY END UP WITH LESS THAN 50 |
| OCCUPANTS, 403.1.3.1 THE USE OF THE BUILDING IS FOR |
| FOOD OR DRINK COMSUMPTION IT WOULD BE REQUIRED BECAUSE |
| OF THE KITHCHEN AREA AND GREASE TO BE CLEANED UP FROM |
| THE FLOOR. |
| |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |