2014-02-27 14:57:07PLUMBNG PLAN REVIEW
 PERMIT: 14011422
 ADD: 847 SOUTHERN BLVD.
 CONT: CARLOS GONZALEZ
 TEL: (561)386-8217
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. FEB.27/ 2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: PROVIDE A COMPLETE
 FLOOR PLAN OF THE BUILDING AND ENTENDED USAGE.
 THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FACILITIES PROVIDE THE OCCUPANT
 LOAD AND COMPLIANCE WITH 2010 PLUMB TABLE 403.1
 2. FIXTURE REQUIREMENTS
 3. WATER SUPPLY PIPING
 4. SANITARY DRAINAGE
 5. WATER HEATERS
 6. VENTS
 78. BACK FLOW PREVENTION
 9. LOCATION OF WATER SUPPLY LINE
 10. GREASE TRAPS
 11 PLUMBING RISER
  
 2) GREASE INTERCEPTOR SHEET 2 INDICATES THE USE OF A
 ATLANTIC METAL WORKS G1-100 PLEASE PROVIDE THE
 MANUFACTURERS SPECS ON THIS UNIT.
 PLEASE PROVIDE SIZING FOR INTERCEPTOR WITH ONE OF THESE
 METHODS 1003.3.4 GREASE INTERCEPTORS AND AUTOMATIC
 GREASE REMOVAL DEVICES.
 GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL
 DEVICES SHALL BE SIZED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 APPENDIX A, OR ASME A112.14.4. GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 BE DESIGNED AND TESTED IN ACCORDANCE WITH PDI G101,
 ASME A112.14.3 OR ASME A112.14.4. GREASE INTERCEPTORS
 AND AUTOMATIC GREASE REMOVAL DEVICES SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER?S INSTRUCTIONS.
 EXCEPTION: GREASE INTERCEPTORS THAT ARE SIZED,
 CONSTRUCTED AND APPROVED IN ACCORDANCE WITH RULE 64E-6,
 FLORIDA ADMINISTRATIVE CODE AND THAT ARE LOCATED
 OUTSIDE THE BUILDING SHALL NOT BE REQUIRED TO MEET THE
 REQUIREMENTS OF THIS SECTION.
  
 3) PROVIDE THE LOCATION OF THE GREASE INTERCEPTOR ON
 THE PLANS.
  
 4) ALSO PROVIDE THE FLOW CONTROL DEVICE WITH THE
 MANUFACTURERS INSTRUCTIONS AND SHOW THE REQUIRED VENT
 FOR THE FLOW CONTROL.
  
 5) THE PLANS DO NOT INDICATE A DISHWASHER OR FOOD
 GRINDER, WILL THERE BE EITHER ONE OR BOTH, THEY WILL
 AFFECT CALCULATIOSN FOR THE AUTOMATIC GREASE REMOVAL
 DEVICE.
  
 6) PLANS DO NOT INDICATE A FLOOR SINK / MOP SINK PART
 OF THE REQUIEMENTS PLUMBING TABLE 403.1 A2 REQUIREMENT,
 EVEN THOUGH THIS MAY END UP WITH LESS THAN 50
 OCCUPANTS, 403.1.3.1 THE USE OF THE BUILDING IS FOR
 FOOD OR DRINK COMSUMPTION IT WOULD BE REQUIRED BECAUSE
 OF THE KITHCHEN AREA AND GREASE TO BE CLEANED UP FROM
 THE FLOOR.
  
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  