2014-02-20 11:47:53 | 14011422 |
| 847 SOUTHERN BLVD |
| REMODEL TO CAFETERIA |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| REVIEW COMMENTS. |
| |
| PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN SHOWING |
| COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 |
| |
| PROVIDE VOLTAGE DROP CALCULATION VERIFYING COMPLIANCE |
| WITH THE ENERGY CODE. FBC-EC 505.7.3 |
| |
| PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING |
| MEANS. NEC 110.22, 110.16, 110.22 |
| |
| PROVIDE DIMENSIONS FOR THE DESIGNATED CLEAR WORKING |
| SPACES REQUIRED AROUND THE ELECTRICAL SERVICE EQUIPMENT |
| AND PANEL BOARDS. NEC 215.5, 110.26 |
| |
| ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS AND |
| WITHIN BATHROOMS MUST BE GFCI PROTECTED. NEC 210.8 |
| |
| SHOW THE LOCATION OF THE ELECTRICAL SERVICE WITH |
| DISCONNECT ON A SITE PLAN WITH PROPERTY LINES. VERIFY |
| THE ELECTRICAL SERVICE MAINS SERVING THIS BUILDING ARE |
| SIX OR LESS AND GROUPED IN ONE LOCATION. SHOW ALL |
| METERS, GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS |
| FOR THE BUILDING SERVICE INCLUDING ALL OTHER EXISTING |
| OCCUPANCIES REQUIRING ELECTRICAL SERVICE. |
| NEC 230.2, 230.71, 230.72 |
| |
| PROVIDE A MAIN SERVICE DISCONNECT AT A READILY |
| ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF |
| THE SERVICE CONDUCTORS. NEC 230.70 |
| |
| VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS HAS A |
| FAULT CURRENT RATING THAT IS SUFFICIENT AT NOMINAL |
| CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| PROVIDE A COMPLETE LOAD CALCULATION. PROVIDE A PANEL |
| SCHEDULE SHOWING ALL LOADS BALANCED. INDICATE THE |
| PROPOSED WIRING METHOD, WIRE SIZE WITH OVER CURRENT |
| PROTECTION FOR ALL CIRCUITS. NEC 220.12; 220.14; |
| 220.12; TABLE 220.12; 230.31 |
| |
| VERIFY THE ELECTRICAL SERVICE LOAD IS NOT LESS THAN THE |
| SUM OF ALL LOADS AS REQUIRED. NEC 215.5; 220.40 |
| |
| PROVIDE A SIGN CIRCUIT. NEC 600.5 |
| |
| PROVIDE GFCI PROTECTED RECEPTACLE FOR SERVICING THE AIR |
| CONDITIONING EQUIPMENT. NEC 210.63 |
| |
| PROVIDE SHOW WINDOW LIGHTING OUTLETS. NEC 210.62 |
| |
| VENDING MACHINES IF PROVIDED SHALL BE PROTECTED WITH |
| GFCI?S. NEC 422.51 |
| |
| PROVIDE A LIGHTING SCHEDULE SHOWING FIXTURE SELECTION |
| INCLUDING EXIT AND EMERGENCY LIGHTING WITH BATTERY BACK |
| UP. FBC, ENERGY CONSERVATION 502.3.8; FBC 1011 |
| |
| VERIFY THE MEANS OF EGRESS HAS EMERGENCY ILLUMINATION |
| AND EXIT SIGNS. FBC 1006.2 1011.1 |
| |
| |
| NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR FIRE |
| ALARM, SECURITY AND DATA SYSTEMS. |
| |
| ROBERT LECKY, CBO |
| ELECTRICAL PLANS REVIEW |
| |
| |