Plan Review Notes
Plan Review Notes For Permit 14011387
Permit Number 14011387
Review Stop P
Sequence Number 1
Notes
Date Text
2014-01-23 17:33:41PLUMBING PLAN REVIEW
 PERMIT: 14011387
 ADD: 1793 PALM BEACH LAKES # W407
 CONT: TO BE DETERMINED
 TEL: (561)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY JAN. 23/2014
 ACTION: DENIED
  
 1) WITH THE OCCUPANT LOAD FOR THIS TENANT, 2 RESTROOMS
 ARE REQUIRED, ONE OF THE RESTROOMS CAN BE COUNTED WITH
 THE COMMON RESTROOMS IN BUILDING J09, THE SECOND
 RESTROOM WILL STILL NEED TO COMPLY WITH 2010 FBC-P
 403.3.1 ACCESS.
 THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY
 SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES
 SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR
 OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE
 ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING
 CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO
 THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE
 BUILDING IS OCCUPIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]